YASKAWA L1000A Technical Manual page 210

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

5.7 H: Terminal Functions
Setting 4: Speed Detection 1
Output opens when the output speed (CLV, CLV/PM) rises above the detection level set in L4-01 plus the detection width
set in L4-02. The terminal remains open until the output speed falls below the level set in L4-01.
Status
Open
Output speed or motor speed exceeded L4-01 + L4-02.
Closed
Output speed or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note: Detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.21
Speed
detection 1
<1> This is the time chart when L4-07 (Speed Agree Detection Selection) is set to 1 (detection always enabled). The default setting for L4-07 is 0
(no detection during baseblock). When L4-07 = 0, the terminal opens during baseblock.
Refer to
L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 229
Setting 5: Speed Detection 2
Output closes whenever the output speed or motor speed (CLV, CLV/PM) is above the detection level set in L4-01. The
terminal remains closed until the output speed or motor speed falls below L4-01 minus the setting of L4-02.
Status
Open
Output speed or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed
Output speed or motor speed exceeded L4-01.
Note: Detection works in both forward and reverse. The value of L4-01 is used as the detection level for both directions.
Figure 5.22
Speed
Detection 2
<1> This is the timing chart when L4-07 (Speed Agree Detection Selection) is set to 1 (detection always enabled). The default setting for L4-07 is 0
(no detection during baseblock). When L4-07 = 0, the terminal opens during baseblock.
Refer to
L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 229
210
Output speed
or motor speed
OFF
ON
<1>
Figure 5.21 Speed Detection 1 Time Chart
Output Speed
or motor speed
OFF
ON
<1>
Figure 5.22 Speed Detection 2 Time Chart
Description
L4-02
L4-01
Description
L4-02
L4-01
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
L4-01
L4-02
common_
TMonly
for more details.
L4-01
L4-02
common_
TMonly
for more details.