Installation Precautions - Mitsubishi Electric FR-F700PJ Instruction Manual

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

1.5.4

Installation precautions

(1)
Above inverter
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be
heat resistant.
(2)
Arrangement of multiple inverters (Filterpacks)
When multiple inverters (Filterpacks) are placed in the
same enclosure, generally arrange them horizontally as
shown in the right figure (a). When it is inevitable to
arrange them vertically to minimize space, take such
measures as to provide guides since heat from the
bottom
inverters
(Filterpacks)
temperatures in the top inverters (Filterpacks), causing
inverter (Filterpack) failures.
When mounting multiple inverters (Filterpacks), fully take
caution not to make the surrounding air temperature of
the inverter (Filterpack) higher than the permissible value
by providing ventilation and increasing the enclosure
size.
(3)
Arrangement of ventilation fan and inverter (Filterpack)
Heat generated in the inverter (Filterpack) is blown up from the
bottom of the unit as warm air by the cooling fan. When
installing a ventilation fan for that heat, determine the place of
ventilation fan installation after fully considering an air flow. (Air
passes through areas of low resistance. Make an airway and
airflow plates to expose the inverter (Filterpack) to cool air.)
Inverter placement (Installation of Filterpack)
Inverter
(Filterpack) (Filterpack)
can
increase
the
(a) Horizontal arrangement
Inverter
Inverter
(Filterpack)
Guide
Inverter
(Filterpack)
Enclosure
Enclosure
Arrangement of multiple inverters (Filterpacks)
Inverter
(Filterpack)
<Good example>
Arrangement of ventilation fan and inverter (Filterpack)
Inverter
(Filterpack)
Guide
Guide
Inverter
(Filterpack)
(b) Vertical arrangement
Inverter
(Filterpack)
<Bad example>
15