4.11.9 Pulse train output of output power (Y79 signal, Pr. 799)

After power ON or inverter reset, output signal (Y79 signal) is output in pulses every time accumulated output power,
which is counted after the Pr.799 Pulse increment setting for output power is set, reaches the specified value (or its integral
multiples).
Parameter
Name
Number
Pulse increment setting for
799
output power
The above parameters can be set when Pr. 160 Extended function display selection = "0".
(1) Pulse increment setting for output power (Y79 signal, Pr.799)
After power ON or inverter reset, output signal (Y79 signal) is output in pulses every time accumulated output power
of the inverter exceeds Pr.799 Pulse increment setting for output power.
The inverter continues to count the output power at retry function or when automatic restart after instantaneous
power failure function works without power OFF of output power (power failure that is too short to cause an inverter
reset), and it does not reset the count.
If power failure occurs, output power is counted from 0kWh again.
Assign pulse output of output power (Y79: setting value 79 (positive logic), 179 (negative logic)) to Pr.190 or Pr.192
(Output terminal function selection).
Pulse output of output power
(Y79)
NOTE
 Because the accumulated data in the inverter is cleared when control power is lost by power failure or at an inverter
reset, the value on the monitor cannot be used to charge electricity bill.
 Changing the terminal assignment using Pr. 190 and Pr. 192 (output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal. (
REMARKS
When parameter copy is performed, Pr.799 = "9999" might be set. However, the inverter operates as Pr.799 were at
"1kWh" (initial value) in such case.
Parameters referred to
Pr. 190, Pr. 192 (output terminal function selection)
Function assignment of external terminal and control
Initial
Setting Range
Value
0.1kWh, 1kWh, 10kWh,
1kWh
100kWh, 1000kWh
Output power
20kWh
10kWh
ON
OFF
ON for 0.15s (0.1 to 0.2s)
When Pr.799 = 10
Refer to page 140
Description
Output signal is output in pulses at every output
power (kWh) that is specified.
Time
Refer to page 140
)
4
149