INVERTER INSTALLATION AND PRECAUTIONS

 Inverter model
• FR-F860-00450 or lower
FR -
F8 0
6
Symbol Voltage class
Symbol
6
600 V class
00027 to 00450
• FR-F860-00680 or higher
FR -
F8 0
6
Symbol Voltage class
Symbol
6
600 V class
00680 to 04420

Inverter equipped with a built-in Ethernet board (FR-A8ETH).
Capacity plate
Inverter model
Serial number
 Inverter placement
Installation on the enclosure
Fix six positions for the FR-F860-02890 or higher.
 Installation environment
Before installation, confirm that the following environment conditions are met.
Item
FR-F860-00090 or lower
Surrounding air
FR-F860-00170 to 01080
temperature

FR-F860-01440 or higher
Ambient humidity
95% RH or less (non-condensing)
Storage temperature
-20 to +65°C
Atmosphere
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude
Maximum 2,500 m
2
Vibration
5.9 m/s

Temperature applicable for a short time, e.g. in transit.

For the installation at an altitude above 1,000 m up to 2,500 m, derate the rated current 3% per 500 m.
2

2.9 m/s
or less for the FR-F860-02890 or higher.

Surrounding air temperature is a temperature measured at a measurement position in an enclosure.
Ambient temperature is a temperature outside an enclosure.

The FR-F860-00680 or higher inverter is intended for installation in an enclosure.
4
INVERTER INSTALLATION AND PRECAUTIONS
-
00027
-
E3
-
N6
Symbol Type
Description
Inverter SLD
E3
CA3
rated current (A)
-
00680
-
E3
-
60
Description
Symbol
Inverter SLD
E3
rated current (A)
• Install the inverter on a strong surface securely with screws.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a nonflammable wall surface.
• When encasing multiple inverters, install them in parallel as a cooling measure.
Allow clearance.

For the FR-F860-00090 or lower, allow 1 cm or more clearance.

For replacing the cooling fan of the FR-F860-02890 or higher, 30 cm of space is necessary in front of the inverter.
Refer to the FR-F860 Instruction Manual (Detailed) for fan replacement.
-10°C to +30°C (non-freezing) (SLD rating)
-10°C to +40°C (non-freezing) (LD rating)
-10°C to +40°C (non-freezing)
-10°C to +40°C (non-freezing) (SLD rating)
-10°C to +50°C (non-freezing) (LD rating)


or less at 10 to 55 Hz (directions of X, Y, Z axes)

Communication type
Symbol
(conforming to IEC60721-3-3 3C2/3S2)
Ethernet∗1
N6
Type
Communication type
Symbol
CA3
Ethernet∗1
Rating plate
Inverter model
Input rating
Output rating
Serial number
Country of origin
Clearances (front)
FR-F860-01080 or lower
10 cm
or more
5 cm
5 cm
or more
or more
∗1
∗1
Vertical
10 cm
or more
Description
Circuit board coating
Plated conductor
With
Without
Circuit board coating
(conforming to IEC60721-3-3 3C2/3S2)
60
With
06
With
Clearances (side)
FR-F860-01440 or higher
20 cm
or more
5 cm
10 cm
10 cm
or more
or more
or more
∗1,∗2
20 cm
or more
Enclosure

5 cm
Measurement
position
UL Type 1
certification
With
Plated
conductor
Without
With
Inverter
Measurement
position
Inverter
5 cm
5 cm