Applied Motor (Pr. 71, Pr. 450) - Mitsubishi Electric FR-F700PJ Instruction Manual

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

4.9.2

Applied motor (Pr. 71, Pr. 450)

Setting of the used motor selects the thermal characteristic appropriate for the motor.
Setting is required when using a constant-torque motor or IPM motor. Thermal characteristic of the electronic thermal
relay function suitable for the motor is set.
When General-purpose magnetic flux vector is selected, the motor constants (SF-JR, SF-HR, SF-JRCA, SF-HRCA,
etc.) necessary for control are selected as well.
Parameter
Name
Number
71
Applied motor
450
Second applied motor
V/F
V/F
V/F
GP
GP
GP
MFVC
MFVC
MFVC
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197)
 Performing IPM parameter initialization changes the settings. (Refer to page 85)
....Specifications differ according to the date assembled. Refer to page 346 to check the SERIAL number.
(1)
Set the motor to be used
Refer to the following list and set the parameter according to the motor used.
Pr. 71 (Pr. 450)
Setting
Pr. 71
Pr. 450
0
Standard motor (such as SF-JR)
(Pr. 71 initial value)
1
Mitsubishi constant-torque motor (such as SF-JRCA)
40
Mitsubishi high-efficiency motor (SF-HR)
50
Mitsubishi constant-torque motor (SF-HRCA)
3
Standard motor
13
Constant-torque motor
23
Mitsubishi standard motor(SF-JR 4P 1.5kW or less)
43
Mitsubishi high-efficiency motor (SF-HR)
53
Mitsubishi constant-torque motor(SF-HRCA)
120
High-efficiency IPM motor (MM-EF)
210
Premium high-efficiency IPM motor MM-EFS
9999
(initial
Without second applied motor
value)
 Performing IPM parameter initialization changes the settings. (Refer to page 85)
REMARKS
 When performing offline auto tuning, set any of "3, 13, 23, 43, 53" in Pr. 71.
(Refer to page 125 for offline auto tuning.)
 For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically changed
according to the Pr. 71 setting as follows. (These are not automatically changed by the Pr.998 IPM parameter initialization setting.)
Automatic Change
Parameter
Pr. 0
Pr. 12

Pr. 71 setting: 0, 3, 23, 40, 43, 120, 210

Pr. 71 setting: 1, 13, 50, 53
NOTE
 Set the electronic thermal relay function to the thermal characteristic for the constant-torque motor when using a
geared motor (GM-S, GM-D, GM-SY, GM-HY2 series) to perform General-purpose magnetic flux vector control.
Initial
Setting Range
Value
0, 1, 3, 13,
0
23, 40, 43, 50, 53,
9999
Used motor
Select "offline auto tuning
Standard Motor
Constant-torque Motor
Setting
Setting
3%
4%
Selection and protection of a motor
Selecting the standard motor, constant-torque
motor, or IPM motor sets the corresponding
120, 210
motor thermal characteristic.
0, 1
Set when using the second motor.
Second motor is invalid.
9999
(Thermal characteristic of the first motor
(Pr. 71))
Thermal Characteristic of the
Electronic Thermal Relay Function
Standard
setting"
2%
2%
Description
Constant-
IPM
torque
123
4