Misoperation prevention and parameter setting restriction
(2)
Disconnected PU detection
This function detects that the PU (FR-PU04/FR-PU07) has been disconnected from the inverter for longer than 1s and
causes the inverter to provide a fault output (E.PUE) and come to trip.
When Pr. 75 is set to any of "0, 1, 14, 15", operation is continued even if the PU is disconnected.
REMARKS
 When the PU has been disconnected since before power-ON, it is not judged as a fault.
 To make a restart, confirm that the PU is connected and then reset the inverter.
 The motor decelerates to a stop when the PU is disconnected during PU Jog operation with Pr. 75 set to any of "0, 1, 14, 15"
(which selects operation to be continued if the PU is disconnected).
 When RS-485 communication operation is performed through the PU connector, the reset selection/PU stop selection function
is valid but the disconnected PU detection function is invalid.
(3)
PU stop selection
In any of the PU operation, External operation and Network operation modes, the motor can be stopped by pressing STOP
key of the operation panel or parameter unit (FR-PU04/FR-PU07, operation panel for FR-E500 (PA02)).
When the inverter is stopped by the PU stop function, "
After the motor is stopped from the PU, it is necessary to perform PU stop (PS) reset to restart. PS reset can be made from
the unit from which PU stop is made (operation panel, parameter unit (FR-PU04/PU07, operation panel for FR-E500
(PA02)).
The motor can be restarted by making PS cancel using a power supply reset or RES signal.
When Pr. 75 is set to any of "0 to 3", PU stop (PS display) is invalid, and deceleration to a stop by
PU operation mode.
REMARKS
During operation in the PU operation mode through RS-485 communication from the PU connector, the motor decelerates to stop
(PU stop) when entered from the operation panel
(4)
How to restart the motor stopped by
(PS) reset method)
Speed
Operation panel
STF
ON
(STR) OFF
Stop/restart example for External operation
The motor can be restarted by making a reset using a power supply reset or RES signal.
REMARKS
 If Pr. 250 Stop selection is set to other than "9999" to select coasting to a stop, the motor will not be coasted to a stop but
decelerated to a stop by the PU stop function during External operation.
194
input from the PU in External operation mode (PU stop
Time
Key
Key
" (PS) is displayed. A fault output is not provided.
.
a) Operation panel
1)After completion of deceleration to a stop, switch OFF the
STF or STR signal.
2)Press
to display
3)Press
to return to
4)Switch ON the STF or STR signal.
b) Parameter unit (FR-PU04/FR-PU07)
1)After completion of deceleration to a stop, switch OFF the
STF or STR signal.
2)Press
........................................ (
3)Switch ON the STF or STR signal.
is valid only in the
............... (
reset)
.
reset)