Mitsubishi Electric FR-F700PJ Instruction Manual page 253

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

Communication operation and setting
 Parameter
Parameter
Register
41000 to
0 to 999
C2(902)
C3(902)
125(903)
C4(903)
C5(904)
C6(904)
126(905)
C7(905)
C22(922)
C23(922)
C24(923)
C25(923)
C42(934)
C43(934)
C44(935)
C45(935)
 Faults history
Register
40501
Fault history 1
40502
Fault history 2
40503
Fault history 3
40504
Fault history 4
40505
Fault history 5
40506
Fault history 6
40507
Fault history 7
40508
Fault history 8
248
Parameter Name
Refer to the parameter list (page
41999
64) for the parameter names.
Terminal 2 frequency setting
41902
bias frequency
Terminal 2 frequency setting bias
42092
(Analog value)
Terminal 2 frequency setting bias
43902
(Terminal analog value)
Terminal 2 frequency setting gain
41903
frequency
Terminal 2 frequency setting gain
42093
(Analog value)
Terminal 2 frequency setting gain
43903
(Terminal analog value)
Terminal 4 frequency setting bias
41904
frequency
Terminal 4 frequency setting bias
42094
(Analog value)
Terminal 4 frequency setting bias
43904
(Terminal analog value)
Terminal 4 frequency setting
41905
gain frequency
Terminal 4 frequency setting gain
42095
(Analog value)
Terminal 4 frequency setting gain
43905
(Terminal analog value)
Frequency setting voltage bias
41922
frequency (built-in
potentiometer)
Frequency setting voltage bias
42112
(built-in potentiometer)
Frequency setting voltage gain
41923
frequency (built-in
potentiometer)
Frequency setting voltage gain
42113
(built-in potentiometer)
41934
PID display bias coefficient
42124
PID display bias analog value
PID display bias analog value
43934
(terminal analog value)
41935
PID display gain coefficient
42125
PID display gain analog value
PID display gain analog value
43935
(terminal analog value)
Definition
Read/
Write
The parameter number + 41000 is the register
Read/write
number.
Read/write
Read/write The analog value (%) set to C3 (902) is read.
The analog value (%) of the voltage applied to the
Read
terminal 2 is read.
Read/write
Read/write The analog value (%) set to C4 (903) is read.
The analog value (%) of the voltage applied to the
Read
terminal 2 is read.
Read/write
Read/write The analog value (%) set to C6 (904) is read.
The analog value (%) of the current (voltage)
Read
applied to the terminal 4 is read.
Read/write
Read/write The analog value (%) set to C7 (905) is read.
The analog value (%) of the current (voltage)
Read
applied to the terminal 4 is read.
Read/write
Read/write The analog value (%) set to C23 (922) is read.
Read/write
Read/write The analog value (%) set to C25(923) is read.
Read/write
Read/write The analog value (%) set to C43 (934) is read.
The analog value (%) of the current (voltage)
Read
applied to the terminal 4 is read.
Read/write
Read/write The analog value (%) set to C45 (935) is read.
The analog value (%) of the current (voltage)
Read
applied to the terminal 4 is read.
Read/write
Read/write
Being 2 bytes in length, the data is stored as
Read
"H00".
Read
Refer to the lowest 1 byte for the error code.
Read
Read
Performing write using the register 40501 batch-
Read
clears the faults history.
Read
Set any value as data.
Read
Remarks
Remarks