Jog Operation (Pr. 15, Pr. 16) - Mitsubishi Electric FR-F700PJ Instruction Manual

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

Frequency setting by external terminals
4.7.2

Jog operation (Pr. 15, Pr. 16)

The frequency and acceleration/deceleration time for Jog operation can be set. Jog operation can be performed in either
of the external and the PU operation mode.
This operation can be used for conveyor positioning, test operation, etc.
Parameter
Name
Number
15
Jog frequency
Jog acceleration/
16
deceleration time
These parameters are displayed as simple mode parameter only when the parameter unit (FR-PU04/FR-PU07) is connected. When the parameter unit is not
connected, the above parameters can be set by setting Pr. 160 Extended function display selection = "0". (Refer to page 197)
* Performing IPM parameter initialization changes the settings. (Refer to page 85)
(1)
Jog operation from outside
When the JOG signal is ON, a start and stop can be made by the start signal (STF, STR).
For the terminal used for Jog operation selection, set "5" in any of Pr.178 to Pr.182 (input terminal function selection) to assign
the function.
Output frequency (Hz)
Pr. 20
Pr. 15 Jog frequency
setting range
Pr. 16
JOG signal
Forward rotation STF
Reverse rotation STR
Operation
1.
Screen at power-ON
 Confirm that the External operation mode is
selected. ([EXT] lit)
If not displayed, press
External (EXT) operation mode. If the
operation mode still does not change, set Pr.
79 to change to the External operation mode.
2.
Turn ON the JOG switch.
3.
Turn the start switch (STF or STR) ON.
 The motor runs while the start switch (STF
or STR) is ON.
 The motor runs at 5Hz. (initial value of Pr.
15)
4.
Turn the start switch (STF or STR) OFF.
REMARKS
 When you want to change the running frequency, change Pr. 15 Jog frequency. (initial value "5Hz")
 When you want to change the acceleration/deceleration time, change Pr. 16 Jog acceleration/deceleration time. (initial value "0.5s")
The acceleration time and deceleration time cannot be set separately for Jog operation.
108
Initial
Setting Range
Value
5Hz
0 to 400Hz
0.5s
0 to 3600s
Forward
rotation
Reverse
rotation
ON
ON
ON
to change to the
Forward
rotation
ON
Forward
rotation
OFF
Frequency for Jog operation.
Acceleration/deceleration time for Jog operation. Acceleration/
deceleration time is the time taken to reach the frequency set in Pr. 20
Acceleration/deceleration reference frequency (initial value is 60Hz).
Acceleration/deceleration time can not be set separately.
Three-phase AC
power supply
Forward rotation
start
Reverse rotation
Time
start
JOG signal
JOG
ON
Reverse
Rotates while ON
rotation
Reverse
rotation
Description
Inverter
R/L
U
1
S/L
V
2
T/L
W
3
STF
STR
JOG
SD
10
2
5
Connection diagram
for external Jog operation
Display