Remote Setting Function (Pr. 59) - Mitsubishi Electric FR-F700PJ Instruction Manual

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

Frequency setting by external terminals
NOTE
 The Pr. 15 setting should be equal to or higher than the Pr. 13 Starting frequency.
 Changing the terminal assignment using Pr.178 to Pr.182 (input terminal function selection) may affect other functions. Set
parameters after confirming the function of each terminal.
 During Jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second
functions are valid. (Refer to page 137))
 When Pr. 79 Operation mode selection = "4", pressing
(FR-PU04/FR-PU07) starts the inverter and pressing
 This function is invalid when Pr. 79 = "3".
Parameters referred to
Pr. 13 Starting frequency
Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments
Pr. 79 Operation mode selection
Pr. 178 to Pr. 182 (input terminal function selection)
4.7.3

Remote setting function (Pr. 59)

Even if the operation panel is located away from the enclosure, you can use contact signals to perform continuous
variable-speed operation, without using analog signals.
By merely setting this parameter, you can use the acceleration, deceleration and setting clear functions of the
remote speed setter (FR-FK).
Parameter
Number
59
Remote function selection
The above parameter can be set when Pr. 160 Extended function display selection = "0". (Refer to page 156)
Inverter
Forward rotation
STF
Acceleration
RH
Deceleration
RM
10
Clear
RL
2
SD
5
Connection diagram
for remote setting
110
Refer to page 116
Refer to page 200
Name
Initial Value
0Hz
0
Acceleration
ON
(RH)
Deceleration
(RM)
Clear (RL)
Forward rotation
(STF)
Power supply
* External running frequency (other than multi-speed) or PU running frequency
of the operation panel and
stops the inverter.
Refer to page 134
Setting
RH, RM, RL signal
Range
0
Multi-speed setting
1
Remote setting
2
Remote setting
0
3
Remote setting
ON
ON
ON
ON
/
of the parameter unit
Refer to page 113
Description
Frequency setting
function
storage function
Not used
Not used
(Turning STF/STR OFF
clears remotely-set
frequency.)
When Pr. 59 = 1, 2
When Pr. 59 = 1
When Pr. 59 = 3
When Pr. 59 = 2, 3
ON
ON
ON
ON
With
Time
ON
ON