IPM motor control <IPM>
4.3.3
IPM motor test operation (Pr.800)
 Without connecting an IPM motor, the frequency movement can be checked by the monitor or analog signal
output.
 Two types of operation can be selected using this parameter: an actual operation by connecting an IPM motor, or
a test operation without connecting an IPM motor to simulate a virtual operation.
Parameter
Number
800
Control method selection
The above parameters can be set when Pr.160 User group read selection = "0." (Refer to page 197)
(1)
Test operation
To activate the IPM motor test operation, set Pr.998 IPM parameter initialization, change the control to IPM motor
control, then set Pr.800 Control method selection = "9."
Perform a test operation by giving a frequency and a start command under each of PU/External/Network operation
mode.
Running frequency
(FM output)
REMARKS
In the test operation, current is not detected and voltage is not output. Related monitor displays of the output current
and voltage show "0."