Frequency setting by analog input (terminal 2, 4)
(c) Adjusting only the frequency without adjusting the gain voltage (current).
(When changing the gain frequency from 60Hz to 50Hz)
Operation
1.
Turn
until
(Pr. 126) appears
2.
Press
to show the present set value.
(60.00Hz)
3.
Turn
to change the set value to
"
". (50.00Hz)
4.
Press
to set.
5.
Mode/monitor check
Press
twice to choose the monitor/
frequency monitor.
6.
Apply a voltage across the inverter terminals 2
and 5 (across 4 and 5) and turn ON the start
command (STF, STR).
Operation starts at 50Hz.
REMARKS
 Changing C4 (Pr. 903) or C7 (Pr. 905) (gain adjustment) value will not change the Pr. 20 Acceleration/deceleration reference
frequency setting.
 For operation from the parameter unit (FR-PU04/FR-PU07), refer to the Instruction Manual of the FR-PU04/FR-PU07.
 When setting the value to 120Hz or more, it is necessary to set Pr. 18 High speed maximum frequency to 120Hz or more. (Refer to
page 101)
 Make the bias frequency setting using the calibration parameter C2 (Pr. 902) or C5 (Pr. 904). (Refer to page 189)
 Refer to page 284 to use the FR-E500 series operation panel (PA02).
Be cautious when setting any value other than "0" as the bias frequency at 0V (0mA). Even if a speed
command is not given, merely turning ON the start signal will start the motor at the preset frequency.
Parameters referred to
Pr. 18 High speed maximum frequency
Pr. 20 Acceleration/deceleration reference frequency
Pr. 125 Terminal 2 frequency setting gain frequency
Pr. 126 Terminal 4 frequency setting gain frequency
Pr. 241 Analog input display unit switchover
C0 (Pr. 900) FM terminal calibration
C2 (Pr. 902) Terminal 2 frequency setting bias frequency
C3 (Pr. 902) Terminal 2 frequency setting bias
C4 (Pr. 903) Terminal 2 frequency setting gain
C5 (Pr. 904) Terminal 4 frequency setting bias frequency
C6 (Pr. 904) Terminal 4 frequency setting bias
C7 (Pr. 905) Terminal 4 frequency setting gain
Bias and gain of built-in frequency setting potentiometer
192
(Pr. 125) or
Flicker...Parameter setting complete!!
Refer to page 101
Refer to page 188
Refer to page 158
Refer to page 188
Refer to page 188
Refer to page 188
Refer to page 188
Display
or
Terminal 2 input
is selected
Hz
A
Hz
A
CAUTION
Refer to page 113
Refer to page 188
Refer to page 188
Refer to page 188
Refer to page 188
Refer to page 284
Terminal 4 input is
selected
Terminal 2 input is
Terminal 4 input is
selected
selected