1

INVERTER INSTALLATION AND PRECAUTIONS

 Inverter model
FR -
F8 0
2
-
00046
Symbol Voltage class
Symbol
00023 to 06830
2
200 V class
0.75 to 315K
4
400 V class

Specification differs by the type. Major differences are shown in the table below.
Type
Monitor output
FM (terminal FM
Terminal FM: pulse train output
Terminal AM: analog voltage output (0 to 10 VDC)
equipped model)
CA (terminal CA
Terminal CA: analog current output (0 to 20 mADC)
Terminal AM: analog voltage output (0 to 10 VDC)
equipped model)

Inverter equipped with a built-in Ethernet board (FR-A8ETH).

Applicable for the FR-F820-00340(7.5K) or higher, and the FR-F840-00170(7.5K) or higher.
Capacity plate
Inverter model
Serial number
NOTE
• In this Instruction Manual, the inverter model name consists of the applicable motor capacity and the rated current. (Example) FR-F820-00046(0.75K)
 Inverter placement
Installation on the enclosure
Fix six positions for the FR-F840-04320(185K) or higher.
 Installation environment
Before installation, confirm that the following environment conditions are met.
Item
LD rating
-10 to +50°C (non-freezing)
Surrounding air
temperature

SLD rating
-10 to +40°C (non-freezing)
With circuit board coating (conforming to IEC60721-3-3 3C2/3S2): 95% RH or less (non-condensing),
Ambient humidity
Without circuit board coating: 90% RH or less (non-condensing)
Storage temperature
-20 to +65°C
Atmosphere
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Altitude
2500 m or lower
Vibration
5.9 m/s

Temperature applicable for a short time, e.g. in transit.

For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per altitude increase of 500 m.
2

2.9 m/s
or less for the FR-F840-04320(185K) or higher.

Surrounding Air Temperature is a temperature measured at a measurement position in an enclosure. Ambient Temperature is a temperature outside an enclosure.

For the amount of heat generated by the inverter unit, refer to the Instruction Manual (Detailed).
-
E1
-
Description
Symbol Type 
Inverter SLD rated current (A)
Inverter LD rated capacity (kW)
E1
E2
Built-in
EMC filter
OFF
ON
Rating plate
Inverter model
Input rating
Output rating
SERIAL
Country of origin
• Install the inverter on a strong surface securely with screws.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a nonflammable wall surface.
• When encasing multiple inverters, install them in parallel as a cooling measure.
• When designing or building an enclosure for the inverter, carefully consider influencing factors such as heat generation
of the contained devices and the operating environment.
Vertical
Allow clearance.

For the FR-F820-00250(5.5K) or lower and FR-F840-00126(5.5K) or lower, allow 1 cm or more clearance.

When using the FR-F820-01250(30K) or lower and FR-F840-00620(30K) or lower at the surrounding air temperature of
40°C or less (30°C or less for the SLD rated inverter), side-by-side installation (0 cm clearance) is available.

For replacing the cooling fan of the FR-F840-04320(185K) or higher, 30 cm of space is necessary in front of the inverter.
Refer to the FR-F800 Instruction Manual (Detailed) for fan replacement.


2
or less at 10 to 55 Hz (directions of X, Y, Z axes)

Communication
Symbol
type
(conforming to IEC60721-3-3 3C2/3S2)
FM
Without
Ethernet 
CA
60
06 
Initial setting
Control
Rated
logic
frequency
Base frequency voltage
9999 (same as the power
Sink logic
60 Hz
supply voltage)
8888 (95% of the power
Source logic
50 Hz
supply voltage)
Clearances (front)
FR-F820-03160(75K) or lower,
FR-F820-03800(90K) or higher,
FR-F840-01800(75K) or lower
FR-F840-02160(90K) or higher
10cm or more
5cm
5cm
10cm
or more∗1,∗2
or more∗1,∗2
or more
10cm or more
Description
INVERTER INSTALLATION AND PRECAUTIONS
Circuit board coating
Plated conductor
Without
Without
With
Without
With
With
Pr.19
Pr.570
Multiple rating setting
1 (LD rating)
0 (SLD rating)
Clearances (side)
20cm or more
5cm
10cm
or more
or more
∗1,∗3
Inverter
20cm or more
Enclosure
Measurement
position
Inverter
5 cm
5 cm
Measurement
5 cm
position
3

Hide quick links:

Advertisement

loading