INVERTER INSTALLATION AND PRECAUTIONS

 Inverter model
FR -
A8 0
2
-
00046
Symbol Voltage class
Symbol
00023 to 06830
2
200 V class
0.4 to 280K
4
400 V class

Specification differs by the type. Major differences are shown in the table below.
Type
FM 
Terminal FM: pulse train output
Terminal AM: analog voltage output (0 to 10 VDC)
(terminal FM equipped model)
CA 
Terminal CA: analog current output (0 to 20 mADC)
Terminal AM: analog voltage output (0 to 10 VDC)
(terminal CA equipped model)

Conforming to IEC 60721-3-3 3C2/3S2

Applicable for the FR-A820-00340(5.5K) or higher, and the FR-A840-00170(5.5K) or higher.
Capacity plate
Inverter model
Serial number
NOTE
• In this Instruction Manual, the inverter model name consists of the applicable motor capacity and the rated current. (Example) FR-A820-00046(0.4K)
 Inverter placement
Installation on the enclosure
Fix six positions for the FR-A840-04320(160K) or higher.
 Installation environment
Before installation, confirm that the following environment conditions are met.
Item
LD, ND (initial setting), HD
Surrounding air
temperature

SLD
Ambient humidity
Storage temperature
Atmosphere
Altitude
Vibration

Temperature applicable for a short time, e.g. in transit.

For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
2

2.9 m/s
or less for the FR-A840-04320(160K) or higher.

Surrounding air temperature is a temperature measured at a measurement position in an enclosure.
Ambient temperature is a temperature outside an enclosure.

For the amount of heat generated by the inverter unit, refer to the Instruction Manual (Detailed).
-
1
-
GF
Description
Symbol Type
Inverter SLD rated current (A)
1
Inverter ND rated capacity (kW)
2
Monitor output
Rating plate
FR-A820-00046-1-GF
Inverter model
Input rating
Output rating
Country of origin
• Install the inverter on a strong surface securely with screws.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a nonflammable wall surface.
• When encasing multiple inverters, install them in parallel as a cooling measure.
• When designing or building an enclosure for the inverter, carefully consider influencing factors such as heat generation
of the contained devices and the operating environment.
Vertical
Allow clearance.

For the FR-A820-00250(3.7K) or lower and FR-A840-00126(3.7K) or lower, allow 1 cm or more clearance.

When using the FR-A820-01250(22K) or lower and FR-A840-00620(22K) or lower at the surrounding air temperature of
40°C or less (30°C or less for the SLD rated inverter), side-by-side installation (0 cm clearance) is available.

For replacing the cooling fan of the FR-A840-04320(160K) or higher, 30 cm of space is necessary in front of the inverter.
Refer to the Instruction Manual (Detailed) for fan replacement.
0 to +50°C (non-freezing)
0 to +40°C (non-freezing)
With circuit board coating (conforming to IEC 60721-3-3 3C2/3S2): 95% RH or less (non-
condensing),
Without circuit board coating: 90% RH or less (non-condensing)
-20 to +65°C

Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Maximum 2500 m

2
5.9 m/s
or less at 10 to 55 Hz (directions of X, Y, Z axes)

∗1
Symbol Circuit board coating
∗2
Plated conductor
FM
None
Without
CA
60
With
06
∗3
With
Initial setting
Built-in
Control logic
EMC filter
OFF
Sink logic
60 Hz
ON
Source logic
50 Hz
SERIAL
Clearances (front)
FR-A820-03160(55K) or lower,
FR-A820-03800(75K) or higher,
FR-A840-01800(55K) or lower
FR-A840-02160(75K) or higher
10 cm
or more
5 cm
5 cm
10 cm
or more
or more
or more
∗1,∗2
∗1,∗2
10 cm
or more
Description
INVERTER INSTALLATION AND PRECAUTIONS
Symbol
Function
With built-in CC-Link IE
Without
GF
Field Network function
Without
With
Rated
Pr.19 Base frequency voltage
frequency
9999 
(same as the power supply voltage)
8888 
(95% of the power supply voltage)
Clearances (side)
20 cm
or more
5 cm
10 cm
or more
or more
∗1,∗3
Inverter
20 cm
or more
Enclosure
Measurement
position
Inverter
5 cm
5 cm
Measurement
5 cm
position
3