4.18.3 Reverse rotation prevention selection (Pr. 78)

This function can prevent reverse rotation fault resulting from the incorrect input of the start signal.
Parameter
Name
Number
Reverse rotation prevention
78
selection
The above parameter can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197)
 Set this parameter when you want to limit the motor rotation to only one direction.
 This parameter is valid for all of the reverse rotation and forward rotation keys of the enclosure surface operation panel and
of parameter unit (FR-PU04/FR-PU07), the start signals (STF, STR signals) via external terminals, and the forward and
reverse rotation commands through communication.

4.18.4 Extended parameter display (Pr. 160)

Parameter which can be read from the operation panel and parameter unit can be restricted.
In the initial setting, only the simple mode parameters are displayed.
Parameter
Name
Number
Extended function display
160
selection
The above parameter allows its setting to be changed during the operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter
write selection.
(1)
Display of simple mode parameters and extended parameters (Pr. 160)
When Pr. 160 = "9999"(initial value), only the simple mode parameters can be displayed on the operation panel and
parameter unit (FR-PU04/FR-PU07). (Refer to the parameter list , page 64, for the simple mode parameters.)
When Pr. 160 = "0", simple mode parameters and extended parameters can be displayed.
REMARKS
 When RS-485 communication is used to read the parameters with Pr. 551 PU mode operation command source selection  "2", all
parameters can be read regardless of the Pr. 160 setting.
 Pr. 15 Jog frequency, Pr. 16 Jog acceleration/deceleration time, and Pr. 991 PU contrast adjustment are displayed as simple mode
parameter when the parameter unit (FR-PU04/FR-PU07) is fitted.
Parameters referred to
Pr. 15
Jog frequency
Jog acceleration/deceleration time
Pr. 16
Pr. 551 PU mode operation command source selection
PU contrast adjustment
Pr. 991
Misoperation prevention and parameter setting restriction
Initial
Value
0
Initial
Value
9999
Refer to page 108
Refer to page 108
Refer to page 214
Refer to page 282
Setting Range
0
Both forward and reverse rotations allowed
1
Reverse rotation disabled
2
Forward rotation disabled
Setting Range
9999
Displays only the simple mode parameters
0
Displays simple mode + extended parameters
Description
Description
197