Bias And Gain Of The Built-In Frequency Setting Potentiometer (C22 (Pr. 922) To C25 (Pr. 923)) - Mitsubishi Electric FR-F700PJ Instruction Manual

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

FR-E500 series operation panel (PA02) setting
4.24.2 Bias and gain of the built-in frequency setting potentiometer (C22 (Pr. 922) to C25
(Pr. 923))
When the operation panel (PA02) for the FR-E500 series is hooked up with the PU cable, the magnitude (slope) of the
output frequency to the frequency setting potentiometer of the operation panel can be set as desired.
Parameter
No.
Frequency setting voltage bias
C22(922)
frequency (built-in potentiometer)
Frequency setting voltage bias (built-
C23(922)
in potentiometer)
C24(923)
Frequency setting voltage gain

frequency (built-in potentiometer)
Frequency setting voltage gain (built-
C25(923)
in potentiometer)

The parameter numbers in parentheses are for the operation panel (PA02) of the FR-E500 series or parameter unit (FR-PU04/FR-PU07).

Performing IPM parameter initialization changes the settings.
The above parameters can be set when Pr. 160 Extended function display selection ="0". (Refer to page 197)
Adjust the bias of the potentiometer of the operation panel
using Pr. 922 (C22, C23) and gain with Pr. 923 (C24, C25).
<Setting>
[Setting from the FR-E500 series operation panel (PA02)]
Bias/gain adjustment methods using the built-in potentiometer are shown below.
 Method to adjust any point by turning the potentiometer.
 Method to adjust any point without turning the potentiometer.
 Method to adjust the bias/gain frequency only.
Set the gain frequency in Pr. 923 to display the analog voltage value of the built-in frequency setting
Method to adjust any
point by turning the
potentiometer.
Set the Pr.79 Operation mode selection value according to the operation mode being used.
284
Name
(Refer to page 85)
Power ON
Make sure that the inverter is in PU mode.
Read Pr. 923 to display the present set gain speed.
potentiometer in %.
Method to adjust only
the gain frequency and
not to adjust the
voltage
Press the
key to shift to the next parameter
Initial
Setting
Value
Range
Frequency on the bias side of PA02 built-in
0Hz
0 to 400Hz
frequency setting potentiometer.
Converted % of the bias side setting level of
0%
0 to 300%
PA02 built-in frequency setting potentiometer.
Frequency on the gain side of PA02 built-in
60Hz
0 to 400Hz
frequency setting potentiometer.
Converted % of the bias side setting level of
100%
0 to 300%
PA02 built-in frequency setting potentiometer.
60Hz
Bias
C22 (Pr. 922)
0
C23 (Pr. 922)
Frequency setting signal
(Built-in frequency setting potentiometer)
Description
Initial value
Gain
C24 (Pr. 923)
100%
C25 (Pr. 923)
Method to adjust any
point without turning
the potentiometer.