Output
frequency
(Hz)
Pr.42
OFF
ON
FU
ON
Example of output frequency detection signal (FU)
REMARKS
All signals are OFF during DC injection brake.
The output frequency compared with the set frequency changes depending on the control method.
Control Method
V/F control
General-purpose magnetic flux
vector control
IPM motor control
NOTE
Changing the terminal assignment using Pr.190 and Pr.192 (output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr. 190, Pr. 192 (output terminal function selection)
Function assignment of external terminal and control
(3) Speed detection hysteresis (Pr.870)
This function prevents chattering of the speed detection
signals.
When an output frequency fluctuates, the up to frequency
Pr.870
signal (SU) and output frequency detection signals (FU) may
repeat ON/OFF (chatters). Setting hysteresis to the detected
frequency prevents chattering of these signals.
OFF
ON
Compared Output Frequency
Output frequency
Output frequency before slip compensation
Estimated frequency (actual motor rotation per minute)
(
Refer to page 140)
REMARKS
Setting a higher value to this parameter slows the
response of frequency detection signals (SU and FU).
4
145