Connection of stand-alone option unit
2.4.3

Connection of the high power factor converter (FR-HC2)

When connecting the high power factor converter (FR-HC2) to suppress power harmonics, perform wiring securely as shown
below. Incorrect connection will damage the FR-HC2 and the inverter.
After making sure that the FR-HC2 is properly connected, set the following parameters.
Pr. 19 Base frequency voltage
Pr. 30 Regenerative function selection (Refer to page 131)
MC
MCCB
AC power
supply

Do not connect anything to the input terminals (R/L1, S/L2, T/L3). Incorrect connection will damage the inverter.

Do not insert an MCCB between the terminals P/+ and N/- (between P and P/+, between N and N/-). Opposite polarity of terminals N/- and P/+ will
damage the inverter.

Use Pr. 178 to Pr. 182 (input terminal function selection) to assign the terminals used for the X10 and RES signals. (Refer to page 134)

Be sure to connect terminal RDY of the FR-HC2 to the X10 signal or MRS signal assigned terminal of the inverter, and connect terminal SE of the
FR-HC2 to terminal SD of the inverter. Without proper connecting, FR-HC2 will be damaged.

Always connect the R/L1, S/L2, and T/L3 terminals of FR-HC2 to the power supply. Operating the inverter without connecting them will
damage FR-HC2.

Do not install an MCCB or MC between the reactor 1 terminals (R/L1, S/L2, T/L3) and FR-HC2 terminals (R4/L14, S4/L24, T4/L34). It will
not operate properly.

Securely perform grounding (earthing) by using the ground (earth) terminal.

Installation of a fuse is recommended. (Refer to the Instruction Manual of FR-HC2.)
NOTE
 The voltage phases of terminals R/L1, S/L2, and T/L3 and terminals R4/L14, S4/L24, and T4/L34 must be matched.
 Match the control logic (sink logic/source logic) of the FR-HC2 and the inverter. (Refer to page 27 )
 Do not connect a DC reactor (FR-HEL) to the inverter when FR-HC2 is connected.
 Filterpack connection is not available when FR-HC2 is connected.
Parameters referred to
Pr. 30 Regenerative function selection
38
Outside box
Reactor1
(FR-HCB2)
(FR-HCL21)
R3/
*6
*6
*6
R2/
R/
R2/
L13
L12
L1
L12
S3/
S/
S2/
S2/
L23
L2
L22
L22
T3/
T/
T2/
T2/
L33
L32
L3
L32
*7
ROH1
ROH2
88R
88S
*7
Refer to page 131
High power
factor converter
Reactor2
(FR-HC2)
(FR-HCL22)
*6
R3/
R4/
R4/L14
L13
L14
S3/
S4/
S4/L24
L24
L23
T3/
T4/
T4/L34
L33
L34
Fuse
*7
P/+
ROH
N/-
SD
RDY
88R
88S
R/L1
RSO
S/L2
*5
SE
T/L3
R1/L11
S1/L21
*7
Inverter
*1
Motor
R/L1
U
S/L2
V
M
T/L3
W
Earth
*8
(ground)
P/+
*2
N/-
*4
X10
*3
RES
*3
SD
*7