4.24 FR-E500 series operation panel (PA02) setting

The operation panel (PA02) for the FR-E500 series can be hooked up with the PU cable for use.
(The inverter can not be directly connected.)
Purpose
Select the frequency setting method
of the operation panel (built-in
potentiometer,
key)
Set the magnitude (slope) of the
output frequency by the built-in
potentiometer as desired.

4.24.1 Built-in potentiometer switching (Pr. 146)

Switches the frequency setting method between the PA02 built-in frequency setting potentiometer and digital frequency
setting by the
Parameter
Name
Number
Built-in potentiometer
146
switching

Set when performing operation using the built-in frequency setting potentiometer using the operation panel (PA02) for the FR-E500 series.
Operation from the inverter operation panel or communication is not available.
The above parameter can be set when Pr.160 Extended function display selection = "0". (Refer to page 197)
FR-E500 series operation panel (PA02) setting
Frequency setting
command selection
Built-in frequency setting
potentiometer bias/gain
key.
Initial Value
1
Parameter that should be Set
Pr. 146
C22(Pr. 922), C23(Pr. 922),
C24(Pr. 923), C25(Pr. 923)
Setting Range
PA02 built-in frequency setting potentiometer valid
0
Frequency setting by the built-in frequency setting
potentiometer
PA02 built-in frequency setting potentiometer invalid
Digital frequency setting by the
Changing frequency continuously by pressing the
1
Hold down the
operation.
Refer to Page
283
284
Description
key.
key.
key to perform
4
283