Table 4 Harmonic Contents (Values at the fundamental current of 100%)
Not used
Used (AC side)
Three-phase bridge
Used (DC side) or with
(Capacitor smoothing)
Filterpack
Used (AC, DC sides)
1) Calculation of equivalent capacity (P0) of harmonic generating equipment
The "equivalent capacity" is the capacity of a 6-pulse converter converted from the capacity of consumer's harmonic
generating equipment and is calculated with the following equation. If the sum of equivalent capacities is higher than the
limit in Table 3, harmonics must be calculated with the following procedure:
P0 = Ki
Pi) [kVA]
Ki: Conversion factor (refer to Table 2)
Pi: Rated capacity of harmonic generating equipment[kVA]
i: Number indicating the conversion circuit type
2) Calculation of outgoing harmonic current
Outgoing harmonic current = fundamental wave current (value converted from received power voltage)  operation ratio 
harmonic content
Operation ratio: Operation ratio = actual load factor  operation time ratio during 30 minutes
Harmonic content: Found in Table 4.
Table 5 Rated Capacities and Outgoing Harmonic Currents for Inverter Drive
Rated
Applicable
Current [A]
Motor (kW)
200V
400V
0.4
1.61
0.81
0.75
2.74
1.37
1.5
5.50
2.75
2.2
7.93
3.96
3.7
13.0
6.50
5.5
19.1
9.55
7.5
25.6
12.8
11
36.9
18.5
15
49.8
24.9
3) Application of the Specific Consumer Guidelines
If the outgoing harmonic current is higher than the maximum value per 1kW contract power  contract power, a harmonic
suppression technique is required.
4) Harmonic suppression techniques
No.
Item
Reactor installation
1
(FR-HAL, FR-HEL)
High power factor converter
2
(FR-HC2)
Installation of power factor
3
improving capacitor
Transformer multi-phase
4
operation
Passive filter
5
(AC filter)
Active filter
6
(Active filter)
Reactor
5th
65
38
14.5
30
28
Fundamental
Rated
Wave Current
Capacity
Converted from
(kVA)
6.6kV (mA)
49
0.57
83
0.97
167
1.95
240
2.81
394
4.61
579
6.77
776
9.07
1121
13.1
1509
17.6
Install an AC reactor (FR-HAL) on the AC side of the inverter or a DC reactor (FR-HEL) on its DC side
or both to suppress outgoing harmonic currents.
(A DC reactor is pre-installed for the inverter with Filterpack.)
This converter trims the current waveform to be a sine waveform by switching in the rectifier
circuit (converter module) with transistors. Doing so suppresses the generated harmonic amount
significantly. Connect it to the DC area of an inverter.
used with the standard accessory.
When used with a series reactor, the power factor improving capacitor has an effect of absorbing
harmonic currents.
Use two transformers with a phase angle difference of 30 as in
effect corresponding to 12 pulses, reducing low-degree harmonic currents.
A capacitor and a reactor are used together to reduce impedances at specific frequencies, producing a
great effect of absorbing harmonic currents.
This filter detects the current of a circuit generating a harmonic current and generates a harmonic
current equivalent to a difference between that current and a fundamental wave current to suppress a
harmonic current at a detection point, providing a great effect of absorbing harmonic currents.
EMC and leakage currents
7th
11th
13th
41
8.5
7.7
7.4
3.4
13
8.4
5.0
9.1
7.2
4.1
* Rated capacity: Determined by the capacity of the applied motor and
found in Table 5. It should be noted that the rated capacity used here is
used to calculate generated harmonic amount and is different from the
power supply capacity required for actual inverter drive.
Outgoing Harmonic Current Converted from 6.6kV(mA)
(No reactor, 100% operation ratio)
5th
7th
11th
13th
31.85
20.09
4.165
3.773
53.95
34.03
7.055
6.391
108.6
68.47
14.20
12.86
156.0
98.40
20.40
18.48
257.1
161.5
33.49
30.34
376.1
237.4
49.22
44.58
504.4
318.2
65.96
59.75
728.7
459.6
95.29
86.32
980.9
618.7
128.3
116.2
Description
The high power factor converter (FR-HC2) is
17th
19th
23rd
4.3
3.1
2.6
3.2
1.9
1.7
4.7
3.2
3.0
3.2
2.4
1.6
17th
19th
23rd
2.107
1.519
1.274
3.569
2.573
2.158
7.181
5.177
4.342
10.32
7.440
6.240
16.94
12.21
10.24
24.90
17.95
15.05
33.37
24.06
20.18
48.20
34.75
29.15
64.89
46.78
39.24
-, - combination to provide an
25th
1.8
1.3
2.2
1.4
25th
0.882
1.494
3.006
4.320
7.092
10.42
13.97
20.18
27.16
3
49