Summary of Contents for Mitsubishi Electric FR-F700PJ
Page 1
INVERTER FR-F700PJ INSTRUCTION MANUAL (Applied) Air-conditioning inverter FR-F720PJ-0.4K to 15K (F) FR-F740PJ-0.4K to 15K (F) OUTLINE WIRING PRECAUTIONS FOR USE OF THE INVERTER PARAMETERS TROUBLESHOOTING PRECAUTIONS FOR MAINTENANCE AND INSPECTION SPECIFICATIONS...
Page 2
Thank you for choosing this Mitsubishi Inverter. This Instruction Manual (Applied) provides instructions for advanced use of the FR-F700PJ series inverters. Incorrect handling might cause an unexpected fault. Before using the inverter, always read this Instruction Manual and the Instruction Manual (Basic) [IB-0600425ENG] packed with the product carefully to use the equipment to its optimum performance.
Page 3
2. Fire Prevention (2) Wiring CAUTION CAUTION Inverter (Filterpack) must be installed on a nonflammable Do not install a power factor correction capacitor or surge wall without holes (so that nobody touches the inverter suppressor/capacitor type filter on the inverter output heatsink on the rear side, etc.).
Page 4
(7) Disposal CAUTION CAUTION The electronic thermal relay function does not guarantee The inverter must be treated as industrial waste. protection motor from overheating. recommended to install both an external thermal and PTC General instruction thermistor for overheat protection. Many of the diagrams and drawings in this Instruction ...
CONTENTS OUTLINE Product checking and parts identification......... 2 Inverter and peripheral devices ............4 1.2.1 Peripheral devices .......................... 5 Removal and reinstallation of the cover ..........6 1.3.1 Front cover............................6 1.3.2 Wiring cover............................ 8 Installation of the inverter and enclosure design......9 1.4.1 Installation environment for the inverter (Filterpack)...............
Page 6
3 PRECAUTIONS FOR USE OF THE INVERTER EMC and leakage currents ..............42 3.1.1 Leakage currents and countermeasures ..................42 3.1.2 EMC measures ..........................45 3.1.3 Power supply harmonics ......................47 3.1.4 Harmonic suppression guideline in Japan ..................48 Installation of power factor improving reactor ........ 50 Power-OFF and magnetic contactor (MC).........
Page 7
V/F pattern..................103 4.6.1 Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47) <V/F> ............... 103 4.6.2 Load pattern selection (Pr. 14) ....................105 Frequency setting by external terminals ........106 4.7.1 Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)... 106 4.7.2 Jog operation (Pr.
Page 8
4.12.3 Reference of the terminal FM (pulse train output) (Pr. 55, Pr. 56) ..........157 4.12.4 Terminal FM calibration (calibration parameter C0 (Pr. 900)) ........... 158 4.12.5 How to calibrate the terminal FM when using the operation panel ..........159 4.13 Operation selection at power failure and instantaneous power failure....................
Page 9
4.19.4 Setting the frequency by analog input (voltage input)..............212 4.19.5 Operation mode at power-ON (Pr. 79, Pr. 340) ................. 213 4.19.6 Start command source and frequency command source during communication operation (Pr. 338, Pr. 339, Pr. 551)..................214 4.20 Communication operation and setting .......... 218 4.20.1 Wiring and configuration of PU connector .................
Page 10
5 TROUBLESHOOTING Reset method of protective function ..........296 List of fault or alarm indications............. 297 Causes and corrective actions ............298 Correspondences between digital and actual characters ..... 308 Check first when you have a trouble ..........309 5.5.1 Motor does not start........................
Page 11
6.2.8 Insulation resistance test using megger ..................328 6.2.9 Pressure test..........................328 SPECIFICATIONS Rating ....................330 Common specifications ..............331 Outline dimension drawings ............333 Specification of the premium high-efficiency IPM motor [MM-EFS (1500r/min) series] ................339 7.4.1 Motor specification........................339 Specification of dedicated IPM motor [MM-EF(1800r/min) series] 340 7.5.1 Motor specification........................
Page 12
<Abbreviation> PU ...........Operation panel and parameter unit (FR-PU04 /FR-PU07 Inverter ..........Mitsubishi inverter FR-F700PJ series F700PJ ........Mitsubishi inverter FR-F700PJ series Pr.............Parameter number (Number assigned to function) PU operation ........Operation using the PU (operation panel/FR-PU04/FR-PU07) External operation ......Operation using the control circuit signals Combined operation......Operation using both the PU (operation panel/FR-PU04/FR-PU07) and External...
Page 14
OUTLINE This chapter explains the "OUTLINE" for use of this product. Always read the instructions before using the equipment. Product checking and parts identification ......... 2 Inverter and peripheral devices........... 4 Removal and reinstallation of the cover ........6 Installation of the inverter and enclosure design ...... 9 Inverter placement (Installation of Filterpack) ......
Product checking and parts identification Product checking and parts identification Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that the product agrees with your order and the inverter is intact. Inverter Inverter model F740PJ -...
RATED installation screw hole SERIAL number SERIAL MITSUBISHI ELECTRIC CORPORATION Crimping terminals for the inverter connection Terminal block cover Black cable: connect to terminal R, S and T of the inverter Red cable: connect to terminal P and P1 of the inverter...
0.5MHz to 5MHz. Inverter A wire should be wound four turns at a FR-F700PJ Earth (Ground) maximum. EMC filter (ferrite core) * Contactor (FR-BSF01, FR-BLF) Example) No-fuse R/L1 S/L2T/L3...
Inverter and peripheral devices 1.2.1 Peripheral devices Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity. Refer to the following list and prepare appropriate peripheral devices. Moulded Case Circuit Breaker (MCCB) or Earth Leakage Circuit Breaker (ELB) ...
Removal and reinstallation of the cover Removal and reinstallation of the cover 1.3.1 Front cover 3.7K or lower Removal (Example of FR-F740PJ-1.5K) 1) Loosen the installation screws of the front cover. (The screws cannot be removed.) 2) Remove the front cover by pulling it like the direction of arrow. Installation screw Reinstallation (Example of FR-F740PJ-1.5K) 1) Place the front cover in front of the inverter, and install it straight.
Page 20
Removal and reinstallation of the cover 5.5K or higher Removal (Example of FR-F740PJ-7.5K) 1) Loosen the installation screws of the front cover. (The screws cannot be removed.) 2) Remove the front cover by pulling it like the direction of arrow with holding the installation hook on the front cover. Installation hook Installation screw...
Removal and reinstallation of the cover 1.3.2 Wiring cover Removal and reinstallation 3.7K or lower Hold the side of the wiring cover, and pull it downward for Also pull the wiring cover downward by holding a removal. frontal part of the wiring cover. To reinstall, fit the cover to the inverter along the guides.
Installation of the inverter and enclosure design Installation of the inverter and enclosure design When an inverter enclosure is to be designed and manufactured, heat generated by contained equipment, etc., the environment of an operating place, and others must be fully considered to determine the enclosure structure, size and equipment layout.
Page 23
Installation of the inverter and enclosure design Dust, dirt, oil mist Dust and dirt will cause such faults as poor contact of contact points, reduced insulation or reduced cooling effect due to moisture absorption of accumulated dust and dirt, and in-enclosure temperature rise due to clogged filter. In the atmosphere where conductive powder floats, dust and dirt will cause such faults as malfunction, deteriorated insulation and short circuit in a short time.
Inverter placement (Installation of Filterpack) 1.4.2 Cooling system types for inverter enclosure From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps, resistors, etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure temperature lower than the permissible temperatures of the in-enclosure equipment including the inverter.
Inverter placement (Installation of Filterpack) NOTE When encasing multiple inverters, install them in parallel as a cooling measure. Install the inverter vertically. For heat dissipation and maintenance, allow minimum clearance shown in the figures below from the inverter to the other devices and to the inner surface of the enclosure.
Inverter placement (Installation of Filterpack) NOTE When encasing multiple inverters, install them in parallel as a cooling measure. Install the inverter (Filterpack) vertically. When installing the Filterpack to the inverter, use the included installation screws for the inverter rear panel. Using a longer screw may damage the Filterpack.
Page 27
Inverter placement (Installation of Filterpack) Underneath installation 10cm or more Filterpack NOTE Install Filterpack with the wiring portion facing right. Underneath installation is not available for 11K and 15K. To release heat, leave clearance of 10cm or more between the inverter and Filterpack. ...
Inverter placement (Installation of Filterpack) 1.5.4 Installation precautions Above inverter Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be heat resistant. Arrangement of multiple inverters (Filterpacks) When multiple inverters (Filterpacks) are placed in the same enclosure, generally arrange them horizontally as shown in the right figure (a).
WIRING This chapter describes the basic "WIRING" for use of this product. Always read the instructions before using the equipment. Wiring..................... 18 Main circuit terminal specifications ..........19 Control circuit specifications ............25 Connection of stand-alone option unit ........34...
Wiring Wiring 2.1.1 Terminal connection diagram Sink logic Main circuit terminal Control circuit terminal With Filterpack *1 Remove the jumper Filterpack . DC reactor (FR-HEL) across the terminals P1 FR-BFP2 Inverter and P/+ to install When connecting a DC reactor, remove the Filterpack.
Main circuit terminal specifications Main circuit terminal specifications 2.2.1 Specification of main circuit terminal Inverter Refer Terminal Terminal Name Description Symbol page R/L1, Connect to the commercial power supply. S/L2, AC power input Do not connect anything to these terminals when using the high power factor T/L3 converter (FR-HC2) or power regeneration common converter (FR-CV).
Main circuit terminal specifications 2.2.2 Terminal arrangement of the main circuit terminal, power supply and the motor wiring Three-phase 200V class FR-F720PJ-0.4K to 0.75K FR-F720PJ-1.5K to 3.7K Jumper Jumper N/- P/+ R/L1 S/L2 T/L3 R/L1 S/L2 T/L3 Motor Power supply Power supply Motor FR-F720PJ-5.5K, 7.5K...
Main circuit terminal specifications Three-phase 400V class FR-F740PJ-0.4K to 3.7K FR-F740PJ-5.5K, 7.5K Jumper Jumper N/- P/+ R/L1 S/L2 T/L3 R/L1 S/L2 T/L3 P/+ PR Power supply Motor Power supply Motor FR-F740PJ-11K, 15K NOTE For the inverters without Filterpacks, make sure P/+ PR R/L1 S/L2 T/L3 the power cables are connected to R/L1, S/L2, and T/L3.
Main circuit terminal specifications 2.2.4 Cables and wiring length Applicable wire size Select the recommended cable size to ensure that a voltage drop will be 2% or less. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency.
Page 36
Main circuit terminal specifications Earthing (Grounding) precautions Always earth (ground) the motor and inverter (Filterpack). 1) Purpose of earthing (grounding) Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before use. An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to manufacture an insulating material that can shut off a leakage current completely, and actually, a slight current flows into the case.
Page 37
Main circuit terminal specifications Total wiring length Under general-purpose motor control Connect one or more general-purpose motors within the total wiring length shown in the following table. 200V class Pr. 72 PWM frequency selection Setting 1.5K 0.4K 0.75K (carrier frequency) or higher 1 (1kHz) or less 300m...
Control circuit specifications Control circuit specifications 2.3.1 Control circuit terminal indicates that terminal functions can be selected using Pr. 178 to Pr. 182, Pr. 190, and Pr. 192 (I/O terminal function selection). (Refer to page 134.) Input signal Refer Terminal Terminal Name Description Rated Specifications...
Control circuit specifications Output signal Terminal Reference Terminal Name Description Rated Specifications Symbol Page 1 changeover contact output indicates that the inverter Contact capacity:230VAC Relay output (fault protective function has activated and the output stopped. 0.3A A, B, C output) Fault: discontinuity across B-C (continuity across A-C), (power factor =0.4) Normal: continuity across B-C (discontinuity across A-C)
Control circuit specifications 2.3.2 Changing the control logic The input signals are set to sink logic (SINK) when shipped from the factory. To change the control logic, the jumper connector above the control terminal must be moved to the other position. Change the jumper connector in the sink logic (SINK) position to source logic (SOURCE) position using tweezers, a pair of long-nose pliers etc.
Page 41
Control circuit specifications (1) Sink logic type and source logic type In sink logic, a signal switches ON when a current flows from the corresponding signal input terminal. Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals. In source logic, a signal switches ON when a current flows into the corresponding signal input terminal.
Control circuit specifications 2.3.3 Wiring of control circuit Control circuit terminal layout Recommend wire size: 0.3mm to 0.75mm RUN SE S1 S2 SC STF STR NOTE Do not remove the shortening wires across the terminals S1 and SC and the terminals S2 and SC. Removing either shortening wire disables the inverter operation.
Page 43
Control circuit specifications 3) Insert the wire into a socket. When using a single wire or a stranded wire without a blade terminal, push an open/close button all the way down with a flathead screwdriver, and insert the wire. Open/close button Flathead screwdriver NOTE ...
Page 44
Control circuit specifications Signal inputs by contactless switches The contacted input terminals of the inverter (STF, STR, RH, RM, AU) can be controlled using a transistor +24V instead of a contacted switch as shown on the right. STF, etc. Inverter External signal input using transistor Wiring instructions 1) It is recommended to use the cables of 0.3mm...
Control circuit specifications 2.3.4 Connection to the PU connector Using the PU connector, you can perform communication operation from the parameter unit (FR-PU07), enclosure surface operation panel (FR-PA07), or a personal computer, etc. Remove the inverter front cover when connecting. When connecting the parameter unit or enclosure surface operation panel using a connection cable Use the optional FR-CB2...
Page 46
Pins No. 2 and 8 provide power to the parameter unit. Do not use these pins for RS-485 communication. When making RS-485 communication with a combination of the FR-F700PJ series, FR-F500J series, FR-E500 series and FR-S500 series, incorrect connection of pins No.2 and 8 (parameter unit power supply) of the above PU connector may result in the inverter malfunction or failure.
Connection of stand-alone option unit Connection of stand-alone option unit The inverter accepts a variety of stand-alone option units as required. Incorrect connection will cause inverter damage or accident. Connect and operate the option unit carefully in accordance with the corresponding option unit manual. 2.4.1 Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR) Install a dedicated brake resistor (MRS type, MYS type, FR-ABR) outside when the motor driven by the inverter is made to run...
Page 48
Connection of stand-alone option unit It is recommended to configure a sequence, which shuts off power in the input side of the inverter by the external thermal relay as shown below, to prevent overheat and burnout of the brake resistor (MRS type, MYS type) and high duty brake resistor (FR-ABR) in case the regenerative brake transistor is damaged.
Connection of stand-alone option unit 2.4.2 Connection of the brake unit (FR-BU2) Connect the brake unit (FR-BU2) as shown below to improve the braking capability at deceleration. If the transistors in the brake unit should become faulty, the resistor can be unusually hot. To prevent unusual overheat and fire, install a magnetic contactor on the inverter's input side to configure a circuit so that a current is shut off in case of fault.
Page 50
Connection of stand-alone option unit Connection example with the FR-BR(-H) type resistor FR-BR MCCB Motor R/L1 Three-phase AC S/L2 power supply T/L3 FR-BU2 Inverter 5m or less Connect the inverter terminals (P/+ and N/-) and brake unit (FR-BU2) terminals so that their terminal names match with each other.
Connection of stand-alone option unit 2.4.3 Connection of the high power factor converter (FR-HC2) When connecting the high power factor converter (FR-HC2) to suppress power harmonics, perform wiring securely as shown below. Incorrect connection will damage the FR-HC2 and the inverter. After making sure that the FR-HC2 is properly connected, set the following parameters.
Connection of stand-alone option unit 2.4.4 Connection of the power regeneration common converter (FR-CV) When connecting the power regeneration common converter (FR-CV), connect the inverter terminals (P/+ and N/-) and power regeneration common converter (FR-CV) terminals as shown below so that their symbols match with each other. R/L1 S/L2 T/L3...
Connection of stand-alone option unit 2.4.5 Connection of a DC reactor (FR-HEL) (1) Keep the surrounding air temperature within the permissible range (-10C to +50C). Keep enough clearance around the reactor because it heats up. (Take 10cm or more clearance on top and bottom and 5cm or more on left and right regardless of the installation direction.) 10cm or more 5cm or more...
PRECAUTIONS FOR USE OF THE INVERTER This chapter explains the "PRECAUTIONS FOR USE OF THE INVERTER" for use of this product. Always read the instructions before using the equipment. EMC and leakage currents ............42 Installation of power factor improving reactor ......50 Power-OFF and magnetic contactor (MC) .........
EMC and leakage currents EMC and leakage currents 3.1.1 Leakage currents and countermeasures Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic noise operation at the increased carrier frequency of the inverter will increase the leakage current.
Page 56
EMC and leakage currents Line-to-line leakage currents Harmonics of leakage currents flowing in static capacitances between the inverter output cables may operate the external thermal relay unnecessarily. When the wiring length is long (50m or more) for the 400V class small-capacity model (7.5kW or less), the external thermal relay is likely to operate unnecessarily because the ratio of the leakage current to the rated motor current increases.
EMC and leakage currents Selection of rated sensitivity current of earth (ground) leakage current breaker When using the earth leakage current breaker with the inverter circuit, select its rated sensitivity current as follows, independently of the PWM carrier frequency. Breaker designed for harmonic and Ig1, Ig2: Leakage currents in wire path during commercial surge suppression...
EMC and leakage currents 3.1.2 EMC measures Some electromagnetic noises enter the inverter to malfunction it, and others are radiated by the inverter to malfunction peripheral devices. Though the inverter is designed to have high immunity performance, it handles low-level signals, so it requires the following basic techniques.
Page 59
EMC and leakage currents Propagation Path Measures When devices that handle low-level signals and are liable to malfunction due to electromagnetic noises, e.g. instruments, receivers and sensors, are contained in the enclosure that contains the inverter or when their signal cables are run near the inverter, the devices may malfunction due to air-propagated electromagnetic noises.
EMC and leakage currents 3.1.3 Power supply harmonics The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power capacitor etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and transmission path. Take the following countermeasure suppression techniques.
Harmonic suppression measures necessary Equal to or less than upper limit Harmonic suppression measures unnecessary Table 2 Conversion Factors for FR-F700PJ Series Class Circuit Type Conversion Factor (Ki) Without reactor K31= 3.4 With reactor (AC side) K32 = 1.8...
Page 62
EMC and leakage currents Table 4 Harmonic Contents (Values at the fundamental current of 100%) Reactor 11th 13th 17th 19th 23rd 25th Not used Used (AC side) 14.5 Three-phase bridge Used (DC side) or with (Capacitor smoothing) Filterpack Used (AC, DC sides) 1) Calculation of equivalent capacity (P0) of harmonic generating equipment The "equivalent capacity"...
Installation of power factor improving reactor Installation of power factor improving reactor When the inverter is connected near a large-capacity power transformer (500kVA or more) or when a power capacitor is to be switched over, an excessive peak current may flow in the power input circuit, damaging the converter circuit. To prevent this, always install a Filterpack or an optional AC reactor (FR-HAL).
Power-OFF and magnetic contactor (MC) Power-OFF and magnetic contactor (MC) Inverter input side magnetic contactor (MC) On the inverter input side, it is recommended to provide an MC for the following purposes. (Refer to page 5 for selection.) 1) To release the inverter from the power supply when the fault occurs or when the drive is not functioning (e.g. emergency stop operation).
Inverter-driven 400V class motor Inverter-driven 400V class motor In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially for a 400V class motor, the surge voltage may deteriorate the insulation. When the 400V class motor is driven by the inverter, consider the following measures: Measures ...
Precautions for use of the inverter Precautions for use of the inverter The FR-F700PJ series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may shorten the product life or damage the product. Before starting operation, always recheck the following items.
Page 67
Precautions for use of the inverter (12) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits. Application of a voltage higher than the permissible voltage to the inverter I/O signal circuits or opposite polarity may damage the I/O devices.
Failsafe of the system which uses the inverter Failsafe of the system which uses the inverter When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an inverter fault occurrence when the detection circuit or output circuit fails, etc.
Page 69
Failsafe of the system which uses the inverter 4)Checking the motor operating status by the start signal input to the inverter and inverter output current detection signal. The output current detection signal (Y12 signal) is output when the inverter operates and currents flows in the motor. Check if Y12 signal is output when inputting the start signal to the inverter (forward signal is STF signal and reverse signal is STR signal).
PARAMETERS This chapter explains the "PARAMETERS" for use of this product. Always read the instructions before using the equipment. The following marks are used to indicate the controls as below. (Parameters without any mark are valid for all controls.) Mark Control method Applied motor (control) V/F control...
Operation panel 4.1.2 Basic operation (factory setting) Operation mode switchover At power-ON (External operation mode) PU Jog operation mode (Example) Value change and frequency flicker alternately. PU operation mode Frequency setting has been (output frequency monitor) written and completed!! (After 1s) General-purpose Set frequency Keep pressing...
Operation panel 4.1.3 Easy operation mode setting (easy setting mode) Setting of Pr. 79 Operation mode selection according to combination of the start command and speed command can be easily made. Changing Start command: external (STF/STR), frequency command: operate with example Operation Display...
Operation panel 4.1.4 Changing the parameter setting value Changing Change the Pr. 1 Maximum frequency setting. example Operation Display Screen at power-ON The monitor display appears. Changing the operation mode PU indicator is lit. Press to choose the PU operation mode. PRM indicator is lit.
Operation panel 4.1.5 Displaying the control method and the set frequency Press the setting dial ( ) to display the present control method. Keep pressing the setting dial in the PU operation mode or in the External/PU combined operation mode 1 (Pr. 79 = "3") to show the presently set frequency.
Parameter list Parameter list Parameter list 4.2.1 Parameter list For simple variable-speed operation of the inverter, the initial setting of the parameters may be used. Set the necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the operation panel.
Page 78
Parameter list Parameter list Control Mode-based Instruction Code Parameter Minimum Refer Correspondence Table Func- Initial Customer Parameter Name Setting Range Setting Parameter Remarks tion Value Setting Increments Page Read Write Extended Copy Clear MFVC MFVC MFVC clear Multi-speed setting (speed 4) 0 to 400Hz, 9999 0.01Hz 9999...
Page 79
Parameter list Parameter list Control Mode-based Instruction Code Parameter Minimum Refer Correspondence Table Func- Initial Customer Parameter Name Setting Range Setting Parameter Remarks tion Value Setting Increments Page Read Write Extended Copy Clear MFVC MFVC MFVC clear Motor capacity 0.4 to 15kW, 9999 0.01kW 9999...
Page 80
Parameter list Parameter list Control Mode-based Instruction Code Parameter Minimum Refer Correspondence Table Func- Initial Customer Parameter Name Setting Range Setting Parameter Remarks tion Value Setting Increments Page Read Write Extended Copy Clear MFVC MFVC MFVC clear Output current detection signal 0 to 10s, 9999 0.1s 0.1s...
Page 81
Parameter list Parameter list Control Mode-based Instruction Code Parameter Minimum Refer Correspondence Table Func- Initial Customer Parameter Name Setting Range Setting Parameter Remarks tion Value Setting Increments Page Read Write Extended Copy Clear MFVC MFVC MFVC clear Life alarm status display (0 to 15) ...
Page 82
Parameter list Parameter list Control Mode-based Instruction Code Parameter Minimum Refer Correspondence Table Func- Initial Customer Parameter Name Setting Range Setting Parameter Remarks tion Value Setting Increments Page Read Write Extended Copy Clear MFVC MFVC MFVC clear Current average time 0.1 to 1s 0.1s ...
Page 83
Parameter list Parameter list Control Mode-based Instruction Code Parameter Minimum Refer Correspondence Table Func- Initial Customer Parameter Name Setting Range Setting Parameter Remarks tion Value Setting Increments Page Read Write Extended Copy Clear MFVC MFVC MFVC clear FM terminal calibration —...
Page 84
Parameter list Parameter list Control Mode-based Instruction Code Parameter Minimum Refer Correspondence Table Func- Initial Customer Parameter Name Setting Range Setting Parameter Remarks tion Value Setting Increments Page Read Write Extended Copy Clear MFVC MFVC MFVC clear Pr.CL Parameter clear 0, 1 Pr.CL —...
Parameters according to purposes IPM motor control <IPM> 4.3.1 Setting procedure of IPM motor control <IPM> ................83 4.3.2 Initializing the parameters required to drive an IPM motor (Pr.998) <IPM>........85 4.3.3 IPM motor test operation (Pr.800) <IPM>..................88 4.3.4 Adjusting the speed control gain (Pr.820, Pr.821) <IPM>...
Page 86
4.11.4 Start signal operation selection (STF, STR, STOP signal, Pr. 250) ........... 138 4.11.5 Output terminal function selection (Pr. 190, Pr. 192)..............140 4.11.6 Detection of output frequency (SU, FU signal, Pr. 41 to Pr. 43, Pr. 870) ........144 4.11.7 Output current detection function (Y12 signal, Y13 signal, Pr.
Page 87
4.18.4 Extended parameter display (Pr. 160) ..................197 4.18.5 Password function (Pr. 296, Pr. 297)..................198 4.19 Selection of operation mode and operation location 4.19.1 Operation mode selection (Pr. 79)....................200 4.19.2 Setting the frequency by the operation panel ................209 4.19.3 Setting the frequency by the operation panel (Pr.
When parameter copy is performed from an FR-F700PJ series inverter, which is set to use MM-EFS under IPM motor control, check that IPM motor control is selected on the operation panel after the copy. (Refer to page 62) ...
IPM motor control <IPM> IPM motor control setting by the operation panel (parameter setting mode) POINT The parameters required to drive an IPM motor are automatically changed as a batch. (Refer to page 85) Initialize the parameter setting for a premium high-efficiency IPM motor (MM-EFS 1500r/min specification) in the Operation example parameter setting mode.
IPM motor control <IPM> Parameters referred to Pr.60 Energy saving control selection Refer to page 174 Pr.72 PWM frequency selection Refer to page 181 Pr.190 or Pr.192 (Output terminal function selection) Refer to page 140 Pr. 261 Power failure stop selection Refer to page 168 Pr.653 Speed smoothing control Refer to page 182...
Page 91
IPM motor control <IPM> IPM parameter initialization list By selecting IPM motor control from the parameter setting mode or with Pr.998 IPM parameter initialization, the parameter settings in the following table change to the settings required to drive an IPM motor. The changed settings differ according to the IPM motor specification (capacity).
Page 92
IPM motor control <IPM> Setting General- IPM motor IPM motor Increment purpose (rotations per Name (frequency) motor minute) 1(MM-EF), 101(MM-EF), 0,101, 1,12 Pr.998 (Initial setting) 12(MM-EFS) 112(MM-EFS) Current average value monitor signal Rated Rated motor current 0.01A output reference current inverter current 10r/min 0.5Hz...
IPM motor control <IPM> 4.3.3 IPM motor test operation (Pr.800) < I P M > Without connecting an IPM motor, the frequency movement can be checked by the monitor or analog signal output. Two types of operation can be selected using this parameter: an actual operation by connecting an IPM motor, or a test operation without connecting an IPM motor to simulate a virtual operation.
Page 94
IPM motor control <IPM> Valid/invalid statuses of I/O terminal functions during the test operation 1)Input terminal function selection (Pr.178 to Pr.182) All assignable functions are valid. 2)Output terminal function selection (Pr. 190 and Pr. 192) Some functions have restrictions. For details, refer to the table below. : invalid : Valid, Signal...
IPM motor control <IPM> 4.3.4 Adjusting the speed control gain (Pr.820, Pr.821) < I P M > Manual adjustment of gain is useful to exhibit the optimum performance of the machine or to improve unfavorable conditions such as vibration and acoustic noise during the operation with high load inertia or gear backlashes. Parameter Initial Setting...
Page 96
IPM motor control <IPM> Adjust in the following procedure: 1) Change the Pr.820 setting while checking the conditions. 2) If it can not be adjusted well, change Pr.821 setting, and perform 1) again. · Movement condition Adjustment method Set Pr.820 and Pr.821 higher. If acceleration is slow, raise the setting by 10%s and set a value that satisfies the Pr.820 following condition: The setting immediately before vibration/noise starts...
Adjustment of the output torque (current) of the motor Adjustment of the output torque (current) of the motor Purpose Parameter that should be Set Refer to Page Set starting torque manually Manual torque boost Pr. 0, Pr. 46 Automatically control output current General-purpose magnetic Pr.
Adjustment of the output torque (current) of the motor 4.4.2 Acquiring large starting torque and low speed torque (General-purpose magnetic flux vector control (Pr. 71, Pr. 80)) MFVC MFVC MFVC General-purpose magnetic flux vector control is available. Large starting torque and low speed torque are available with General-purpose magnetic flux vector control. ...
Page 99
Adjustment of the output torque (current) of the motor Selection method of General-purpose magnetic flux vector control Perform secure wiring. (Refer to page 18) Display the extended function parameters. (Pr. 160) (Refer to page 197) Set "0" in Pr. 160 to display the extended function parameters. Set the motor.
Adjustment of the output torque (current) of the motor 4.4.3 Slip compensation (Pr. 245 to Pr. 247) MFVC MFVC MFVC <V/F><GP MFVC> Inverter output current may be used to assume motor slip to keep the motor speed constant. Parameter Name Initial Value Setting Range Description...
Adjustment of the output torque (current) of the motor 4.4.4 Stall prevention operation (Pr. 22, Pr. 23, Pr. 48, Pr. 66, Pr. 154, Pr. 156, Pr. 157) This function monitors the output current and automatically changes the output frequency to prevent the inverter from coming to trip due to overcurrent, overvoltage, etc.
Page 102
Adjustment of the output torque (current) of the motor Setting of stall prevention operation level (Pr. 22) For Pr. 22, set the output current level where the stall prevention is activated. Set the output current level in ratio to Output current the rated inverter current (rated IPM motor current under IPM Pr.
Page 103
Adjustment of the output torque (current) of the motor Setting of stall prevention operation in high frequency range (Pr. 22, Pr. 23, Pr. 66) MFVC MFVC MFVC Setting example (Pr. 22 = 120%, Pr. 23 = 100%, Pr. 66 = 60Hz) Pr.
Page 104
Adjustment of the output torque (current) of the motor To further prevent a trip (Pr.154) Set Pr.154 = "11" when the overvoltage protective function (E.OV ) activates during stall prevention operation in an application with large load inertia. Note that turning OFF the start signal (STF/STR) or varying the frequency signal during stall prevention operation may delay the acceleration/deceleration start.
Page 105
Adjustment of the output torque (current) of the motor CAUTION Do not set a small value as the stall prevention operation current. Otherwise, torque generated will reduce. Test operation must be performed. Stall prevention operation during acceleration may increase the acceleration time. Stall prevention operation performed during constant speed may cause sudden speed changes.
Limiting the output frequency Limiting the output frequency Purpose Parameter that should be Set Refer to Page Set upper limit and lower limit of Maximum/minimum Pr. 1, Pr. 2, Pr. 18 output frequency frequency Perform operation by avoiding Frequency jump Pr.
Limiting the output frequency 4.5.2 Avoiding mechanical resonance points (frequency jumps) (Pr. 31 to Pr. 36, Pr. 552) When it is desired to avoid resonance attributable to the natural frequency of a mechanical system, these parameters allow resonant frequencies to be jumped. Parameter Name Initial Value...
V/F pattern V/F pattern Purpose Parameter that should be Set Refer to Page Base frequency, Set motor ratings Pr. 3, Pr. 19, Pr. 47 Base frequency voltage Select a V/F pattern according to Load pattern selection Pr. 14 applications. 4.6.1 Base frequency, voltage (Pr.
Page 109
V/F pattern Base frequency voltage setting (Pr. 19) Use Pr. 19 Base frequency voltage to set the base voltage (e.g. rated motor voltage). If the setting is less than the power supply voltage, the maximum output voltage of the inverter is as set in Pr. 19. ...
V/F pattern 4.6.2 Load pattern selection (Pr. 14) Optimum output characteristic (V/F characteristic) for the application and load characteristics can be selected. Parameter Name Initial Value Setting Range Description Number For constant-torque load Load pattern selection For variable-torque load The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197) Constant-torque load application (setting "0") Pr.
Frequency setting by external terminals Frequency setting by external terminals Purpose Parameter that should be Set Refer to Page Make frequency setting by Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Multi-speed operation combination of terminals Pr. 232 to Pr. 239 Perform Jog operation Jog operation Pr.
Page 112
Frequency setting by external terminals Multi-speed setting for 4 or more speeds (Pr. 24 to Pr. 27, Pr. 232 to Pr. 239) Frequency from 4th speed to 15th speed can be set according to the combination of the RH, RM, RL and REX signals. Set the running frequencies in Pr.
Frequency setting by external terminals 4.7.2 Jog operation (Pr. 15, Pr. 16) The frequency and acceleration/deceleration time for Jog operation can be set. Jog operation can be performed in either of the external and the PU operation mode. This operation can be used for conveyor positioning, test operation, etc. Parameter Initial Name...
Page 114
Frequency setting by external terminals Jog operation from PU Select Jog operation mode from the operation panel and PU (FR-PU04/FR-PU07). Operation is performed only while the start button is pressed. Inverter R/L1 Three-phase AC S/L2 Motor power supply T/L3 Operation panel Operation Display Confirmation of the operation status indicator...
Frequency setting by external terminals NOTE The Pr. 15 setting should be equal to or higher than the Pr. 13 Starting frequency. Changing the terminal assignment using Pr.178 to Pr.182 (input terminal function selection) may affect other functions. Set parameters after confirming the function of each terminal.
Page 116
Frequency setting by external terminals Remote setting function Use Pr. 59 to select whether the remote setting function is used or not and whether the frequency setting storage function in the remote setting mode is used or not. When Pr. 59 is set to any of "1 to 3" (remote setting function valid), the functions of the RH, RM and RL signals are changed to acceleration (RH), deceleration (RM) and clear (RL).
Page 117
Frequency setting by external terminals REMARKS The RH and RM signals are assigned to the terminals RH and RM in the initial setting. By setting "1 (RM)" or "2 (RH)" in any of Pr. 178 to Pr. 182 (input terminal function selection), you can assign the signals to other terminals. During Jog operation or PID control operation, the remote setting function is invalid.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern Setting of acceleration/deceleration time and acceleration/ deceleration pattern Purpose Parameter that should be Set Refer to Page Pr. 7, Pr. 8, Pr. 20, Pr. 44, Pr. 45, Motor acceleration/deceleration time Acceleration/deceleration setting times Pr.
Page 119
Setting of acceleration/deceleration time and acceleration/ deceleration pattern Deceleration time setting (Pr. 8, Pr. 20) Use Pr. 8 Deceleration time to set the deceleration time required to reach 0Hz from Pr. 20 Acceleration/deceleration reference frequency. Set the deceleration time according to the following formula. Deceleration Pr.
Page 120
Setting of acceleration/deceleration time and acceleration/ deceleration pattern (4) Setting the acceleration/deceleration time in the low-speed range (Pr.791, Pr.792) If torque is required in the low-speed range (rated motor frequency/10), set the Pr.791 Acceleration time in low-speed range and Pr.792 Deceleration time in low-speed range settings higher than the Pr.7 Acceleration time and Pr.8 Deceleration time (When the second function is enabled, the setting is applied.) settings so that the slow acceleration/deceleration is performed in the low-speed range.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern 4.8.2 Starting frequency and start-time hold function (Pr. 13, Pr. 571) MFVC MFVC MFVC <V/F><GP MFVC> You can set the starting frequency and hold the set starting frequency for a certain period of time. Set these functions when you need the starting torque or want to smooth motor drive at a start.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern 4.8.3 Minimum motor rotation frequency (Pr.13) <IPM> Set the frequency where the motor starts running. Set the deadband in the low-speed range to eliminate noise and offset deviation when setting a frequency with analog input.
Setting of acceleration/deceleration time and acceleration/ deceleration pattern 4.8.4 Acceleration/deceleration pattern (Pr. 29) You can set the acceleration/deceleration pattern suitable for application. Parameter Name Initial Value Setting Range Description Number Linear acceleration/ deceleration Acceleration/deceleration S-pattern acceleration/deceleration A pattern selection S-pattern acceleration/deceleration B The above parameters can be set when Pr.
Selection and protection of a motor Selection and protection of a motor Purpose Parameter that should be Set Refer to Page Electronic thermal O/L relay Motor protection from overheat Pr. 9, Pr. 51, Pr. 561 PTC thermistor protection Use the constant-torque motor Applied motor Pr.
Page 125
Selection and protection of a motor (2) Electronic thermal O/L relay operation under IPM motor control (Pr.9) This function detects the overload (overheat) of the motor and trips the inverter by stopping the operation of the transistor at the inverter output side. (The operation characteristic is shown below.) ...
Page 126
Selection and protection of a motor Set two different electronic thermal O/L relays (Pr. 51) MFVC MFVC MFVC Use this function when running two motors of different rated currents individually by a single inverter. (When running two motors together, use external thermal relays.) Set the rated current of the second motor to Pr.
Page 127
Selection and protection of a motor PTC thermistor protection (Pr. 561) Inverter Motor Terminal 2 and terminal 10 are available for inputting of motor built-in PTC thermistor output. When the PTC thermistor input reaches to the resistance value set in Pr. 561 PTC thermistor protection level, inverter outputs PTC thermistor operation error PTC thermistor input connection signal (E.PTC) and trips.
Selection and protection of a motor 4.9.2 Applied motor (Pr. 71, Pr. 450) Setting of the used motor selects the thermal characteristic appropriate for the motor. Setting is required when using a constant-torque motor or IPM motor. Thermal characteristic of the electronic thermal relay function suitable for the motor is set.
Page 129
Selection and protection of a motor To use two types of motors (Pr. 450) MFVC MFVC MFVC Set Pr. 450 Second applied motor to use two different motors with one inverter. When "9999" (initial value) is set, no function is selected. ...
Selection and protection of a motor 4.9.3 Exhibiting the best performance for the motor (offline auto tuning) (Pr. 71, Pr. 80, Pr. 82 to Pr. 84, Pr. 90, Pr. 96) MFVC MFVC MFVC <GP MFVC> The motor performance can be maximized with offline auto tuning. What is offline auto tuning? When performing General-purpose magnetic flux vector control, the motor can be run with the optimum operating characteristics by automatically measuring the motor constants (offline auto tuning) even when each motor constants...
Page 131
Selection and protection of a motor Before performing offline auto tuning Check the following before performing offline auto tuning. Make sure General-purpose magnetic flux vector control (Pr. 80) is selected. A general-purpose motor (three-phase induction motor) should be connected. Note that the motor should be at a stop at a tuning start.
Page 132
Selection and protection of a motor Execution of tuning POINT Before tuning, check the monitor display of the operation panel or parameter unit (FR-PU04/FR-PU07) to confirm that the inverter is in the suitable condition for tuning. (Refer to 2) below.) Turning ON the start command in a tuning-disabled status starts the motor running.
Page 133
Selection and protection of a motor 3) When offline auto tuning ends, press of the operation panel during PU operation. For External operation, turn OFF the start signal (STF signal or STR signal) once. This operation resets the offline auto tuning and the PU's monitor display returns to the normal indication. (Without this operation, next operation cannot be started.) REMARKS ...
Motor brake and stop operation 4.10 Motor brake and stop operation Purpose Parameter that should be Set Refer to Page DC Injection brake of general- Pr. 10 to Pr. 12 purpose motor control Motor braking torque adjustment DC injection brake of IPM Pr.
Motor brake and stop operation CAUTION Install a mechanical brake to make an emergency stop or to stay stopped for a long time. Parameters referred to Pr. 13 Starting frequency Refer to page 116 Pr. 71 Applied motor Refer to page 123 4.10.2 DC injection brake of IPM motor control (Pr.10, Pr.11) <...
Motor brake and stop operation 4.10.3 Selection of a regenerative brake (Pr. 30, Pr. 70) When making frequent starts/stops, use the optional brake resistor (MRS type, MYS type), high-duty brake resistor (FR-ABR) and brake unit (FR-BU2) to increase the regenerative brake duty. ...
Page 137
Motor brake and stop operation When a high power factor converter (FR-HC2) is used and automatic restart after instantaneous power failure function is valid When automatic restart after instantaneous power failure function of both the FR-HC2 and inverter is valid (when a value other than "9999"...
Motor brake and stop operation 4.10.4 Stop selection (Pr. 250) Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns OFF. Used to stop the motor with a mechanical brake, etc. together with switching OFF of the start signal. You can also select the operations of the start signals (STF/STR).
Function assignment of external terminal and control 4.11 Function assignment of external terminal and control Purpose Parameter that should be Set Refer to Page Input terminal function Assign function to input terminal Pr. 178 to Pr. 182 selection Set MRS signal (output shutoff) to MRS input selection Pr.
Page 140
Function assignment of external terminal and control Input terminal function assignment Using Pr. 178 to Pr. 182, set the functions of the input terminals. Refer to the following table and set the parameters: Refer to Setting Signal Function Related Parameters Page Pr.
Function assignment of external terminal and control 4.11.2 Inverter output shutoff signal (MRS signal, Pr. 17) The inverter output can be shut off by the MRS signal. Also, logic for the MRS signal can be selected. Parameter Name Initial Value Setting Range Description Number...
Function assignment of external terminal and control 4.11.3 Condition selection of function validity by second function selection signal (RT) You can select the second function using the RT signal. When the RT signal turns ON, the second function becomes valid. ...
Function assignment of external terminal and control 4.11.4 Start signal operation selection (STF, STR, STOP signal, Pr. 250) You can select the operation of the start signal (STF/STR). Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns OFF. Used to stop the motor with a mechanical brake, etc.
Page 144
Function assignment of external terminal and control Three-wire type (STF, STR, STOP signal) The three-wire connection is shown below. Turning the STOP signal ON makes start self-holding function valid. In this case, the forward/reverse rotation signal functions only as a start signal. If the start signal (STF or STR) is turned ON and then OFF, the start signal is held and makes a start.
Function assignment of external terminal and control 4.11.5 Output terminal function selection (Pr. 190, Pr. 192) You can change the functions of the open collector output terminal and relay output terminal. Parameter Initial Name Initial Signal Setting Range Number Value 0, 1, 3, 4, 7, 8, 11 to 16, 25, 26, 46 RUN terminal Open collector...
Page 146
Function assignment of external terminal and control Setting Refer Related Signal Function Operation Positive Negative Parameter Page logic logic Pr. 71, Pr. 80, IPM motor control Output during IPM motor control. Pr. 998 Pr. 65 to During retry Output during retry processing. Pr.
Page 147
Function assignment of external terminal and control Inverter operation ready signal (RY signal) and inverter running signal (RUN signal) Power supply DC injection brake operation point DC injection brake operation Pr. 13 Starting frequency Time Reset processing When the inverter is ready to operate, the output of the operation ready signal (RY) is ON. (It is also ON during inverter running.) ...
Page 148
Function assignment of external terminal and control Fault output signal (ALM signal) Inverter fault occurrence If the inverter trips, the ALM signal is output. (Trip) Output frequency Time ON OFF Reset processing (about 1s) Reset ON REMARKS The ALM signal is assigned to the ABC contact in the initial setting. By setting "99 (positive logic) or 199 (negative logic) in Pr.190 or Pr.192 (output terminal function selection), the ALM signal can be assigned to the other signal.
Function assignment of external terminal and control 4.11.6 Detection of output frequency (SU, FU signal, Pr. 41 to Pr. 43, Pr. 870) The inverter output frequency is detected and output at the output signals. Parameter Name Initial Value Setting Range Description Number Up-to-frequency...
Page 150
Function assignment of external terminal and control (3) Speed detection hysteresis (Pr.870) Output This function prevents chattering of the speed detection frequency (Hz) signals. When an output frequency fluctuates, the up to frequency Pr.42 Pr.870 signal (SU) and output frequency detection signals (FU) may repeat ON/OFF (chatters).
Function assignment of external terminal and control 4.11.7 Output current detection function (Y12 signal, Y13 signal, Pr. 150 to Pr. 153, Pr. 166, Pr. 167) The output current during inverter running can be detected and output to the output terminal. Parameter Setting Name...
Page 152
Function assignment of external terminal and control Zero current detection (Y13 signal, Pr. 152, Pr. 153) If the output current remains lower than the Pr. 152 setting during inverter operation for longer than the time set in Pr. 153, the zero current detection (Y13) signal is output from the inverter's open collector or relay output terminal.
Function assignment of external terminal and control 4.11.8 Remote output selection (REM signal, Pr. 495, Pr. 496) You can utilize the ON/OFF of the inverter's output signals instead of the remote output terminal of the programmable logic controller. Parameter Initial Setting Name Description...
Function assignment of external terminal and control 4.11.9 Pulse train output of output power (Y79 signal, Pr. 799) After power ON or inverter reset, output signal (Y79 signal) is output in pulses every time accumulated output power, which is counted after the Pr.799 Pulse increment setting for output power is set, reaches the specified value (or its integral multiples).
Monitor display and monitor output signal 4.12 Monitor display and monitor output signal Refer to Purpose Parameter that should be Set Page Display motor speed Speed display and speed setting Pr. 37, Pr. 144, Pr. 505 Set speed Monitor display/PU main display Pr.
Page 156
Monitor display and monitor output signal NOTE Under V/F control, the output frequency of the inverter is displayed in terms of synchronous speed, and therefore, displayed value = actual speed + motor slip. The display changes to the actual speed (estimated value calculated based on the motor slip) when slip compensation was valid.
Monitor display and monitor output signal 4.12.2 Monitor display selection of DU/PU and terminal FM (Pr. 52, Pr. 54, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891) The monitor to be displayed on the main screen of the operation panel and parameter unit (FR-PU04/FR-PU07) can be selected.
Page 158
Monitor display and monitor output signal Pr. 52 Setting Operation Pr. 54 (FM) Terminal FM Types of Monitor Unit Description panel main Setting Full Scale Value monitor Regenerative brake 0.1% Brake duty set in Pr. 30, Pr. 70 Pr. 70 duty Displays the thermal cumulative value on Electronic thermal...
Page 159
Monitor display and monitor output signal Pr. 52 Setting Operation Pr. 54 (FM) Terminal FM Types of Monitor Unit Description panel main Setting Full Scale Value monitor Displays the PTC thermistor resistance at PTC thermistor terminal 2 when PTC thermistor protection ...
Page 160
Monitor display and monitor output signal Operation panel I/O terminal monitor (Pr. 52) When Pr. 52 = "55", the I/O terminal status can be monitored on the operation panel. The I/O terminal monitor is displayed on the third monitor. The LED is ON when the terminal is ON, and the LED is OFF when the terminal is OFF. The center line of LED is always On the I/O terminal monitor (Pr.
Page 161
Monitor display and monitor output signal Cumulative energization time and actual operation time monitor (Pr. 171, Pr. 563, Pr. 564) Cumulative energization time monitor (Pr. 52 = "20") accumulates energization time from shipment of the inverter every one hour. On the actual operation time monitor (Pr. 52 = "23"), the inverter running time is added up every hour. (Time is not added up during a stop.) If the monitored value exceeds 65535, it is added up from 0.
Monitor display and monitor output signal 4.12.3 Reference of the terminal FM (pulse train output) (Pr. 55, Pr. 56) The pulse train output terminal FM is available for monitor output. Set the reference of the signal output from terminal FM. Parameter Name Initial Value...
Monitor display and monitor output signal 4.12.4 Terminal FM calibration (calibration parameter C0 (Pr. 900)) By using the operation panel or parameter unit, you can calibrate terminal FM to full scale deflection. Parameter Name Initial Value Setting Range Description Number Calibrates the scale of the meter C0 (900) FM terminal calibration...
Monitor display and monitor output signal 4.12.5 How to calibrate the terminal FM when using the operation panel Perform the following procedure to calibrate terminal FM using the operation panel FR-DU07. Refer to page 158 for the details of parameters. Operation Display (When Pr.
Page 165
Monitor display and monitor output signal REMARKS Calibration can also be made for External operation. Set the frequency in the External operation mode, and make calibration in the above procedure. Calibration can be made even during operation. For operation from the parameter unit (FR-PU04/FR-PU07), refer to the Instruction Manual of the parameter unit. Parameters referred to Pr.
Operation selection at power failure and instantaneous power failure 4.13 Operation selection at power failure and instantaneous power failure Purpose Parameter that should be Set Refer to Page At instantaneous power failure Pr. 30, Pr. 57, Pr. 58, Pr. 96, Automatic restart operation occurrence, restart inverter without after instantaneous power...
Page 167
Operation selection at power failure and instantaneous power failure When Pr. 162 = 1, 11 (without frequency search) Automatic restart operation selection (Pr. 30, Pr. 162, Pr. 299) Instantaneous (power failure) time Without frequency search Power supply When Pr. 162 = "1 (initial value) or 11", automatic restart (R/L1, S/L2, T/L3) operation is performed in a reduced voltage system, where the voltage is gradually risen with the output...
Page 168
Operation selection at power failure and instantaneous power failure Restart operation at every start When Pr. 162 = "10 or 11", automatic restart operation is also performed every start, in addition to the automatic restart after instantaneous power failure. When Pr. 162 = "0", automatic restart operation is performed at the first start after power supply ON, but not performed at the second time or later.
Page 169
Operation selection at power failure and instantaneous power failure Setting 1) Set "21" in Pr. 96 Auto tuning setting/status. Tuning is performed without motor running. 2) Set the rated motor current (initial value is rated inverter current) in Pr. 9 Electronic thermal O/L relay. (Refer to page 119) 3) Set Pr.
Page 170
Operation selection at power failure and instantaneous power failure 3) When offline auto tuning ends, press of the operation panel during PU operation. For External operation, turn OFF the start signal (STF signal or STR signal) once. This operation resets the offline auto tuning and the PU's monitor display returns to the normal indication. (Without this operation, next operation cannot be started.) 4) If offline auto tuning ended in error (see the table below), frequency search gain are not set.
Operation selection at power failure and instantaneous power failure 4.13.2 Automatic restart after instantaneous power failure/flying start under IPM motor control (Pr. 57, Pr. 162, Pr. 611) <IPM> You can restart the inverter without stopping the motor in the following cases: When power comes back ON after an instantaneous power failure ...
Page 172
Operation selection at power failure and instantaneous power failure (3) Automatic restart operation adjustment (Pr. 611) Using Pr. 611, the acceleration time to reach Pr. 20 Acceleration/deceleration reference frequency can be set. This can be set separately from the normal acceleration time. REMARKS Even if the Pr.
Operation selection at power failure and instantaneous power failure 4.13.3 Power-failure deceleration stop function (Pr. 261) MFVC MFVC MFVC <V/F><GP MFVC> When a power failure or undervoltage occurs, the inverter can be decelerated to a stop or can be decelerated and re- accelerated to the set frequency.
Page 174
Operation selection at power failure and instantaneous power failure Operation continuation at instantaneous power failure function (Pr. 261 = "2") When power is restored during deceleration after a power failure, acceleration is made again up to the set frequency. ...
Operation setting at fault occurrence 4.14 Operation setting at fault occurrence Purpose Parameter that should be Set Refer to Page Recover by retry operation at fault Retry operation Pr. 65, Pr. 67 to Pr. 69 occurrence Do not output input/output phase Input/output phase failure Pr.
Page 176
Operation setting at fault occurrence During a retry, the Y64 signal is ON. For the Y64 signal, assign the function by setting "64 (positive operation)" or "164 (negative operation)" to Pr. 190 or Pr. 192 (output terminal function selection) . ...
Operation setting at fault occurrence 4.14.2 Input/output phase loss protection selection (Pr. 251, Pr. 872) You can choose whether to make Input/output phase loss protection valid or invalid. Output phase loss protection is a function to stop the inverter output if one of the three phases (U, V, W) on the inverter's output side is lost.
Operation setting at fault occurrence 4.14.4 Overspeed detection function (Pr.374) Inverter outputs are stopped when the motor speed exceeds the Pr.374 Overspeed detection level under IPM motor control. Parameter Name Initial value Setting range Description Number When the motor speed exceeds the speed set in Pr.374, overspeed (E.OS) 0 to 400Hz Overspeed detection level...
Energy saving operation and energy saving monitor 4.15 Energy saving operation and energy saving monitor Purpose Parameter that should be Set Refer to Page Energy saving operation Optimum excitation control Pr. 60 Pr. 52, Pr. 54, Pr. 158, How much energy can be saved Energy saving monitor Pr.
Energy saving operation and energy saving monitor 4.15.2 Energy saving monitor (Pr. 891 to Pr. 899) From the power consumption estimated value during commercial power supply operation, the energy saving effect by use of the inverter can be monitored/output. Parameter Name Initial Value Setting Range...
Page 181
Energy saving operation and energy saving monitor (1) Energy saving monitor list Energy Saving Category Description Remarks Monitored Item Displays the real-time energy savings based on the following calculation: The (estimated) power consumption during the 1) Power saving Real-time energy saving commercial power supply operation - the input power 2) Power saving rate to the inverter...
Page 182
Energy saving operation and energy saving monitor Details of the energy saving monitors (Pr. 52 and Pr. 54 = "50") Parameter Setting Energy Saving Description and Formula Unit Monitored Item Pr. 895 Pr. 896 Pr. 897 Pr. 899 Difference between the estimated value of power necessary for commercial power supply operation Power saving and the input power calculated by the inverter...
Page 183
Energy saving operation and energy saving monitor (2) Power saving instantaneous monitor ( 1) power savings, 2) power saving rate ) On the power saving monitor ( 1)), an energy saving effect as compared to the power consumption during commercial power supply operation (estimated value) is calculated and displays on the main monitor.
Page 184
Energy saving operation and energy saving monitor (5) Power estimated value of commercial power supply operation (Pr. 892, Pr. 893, Pr. 894) Select the commercial power supply operation pattern from among the four patterns of discharge damper control (fan), inlet damper control (fan), valve control (pump) and commercial power supply drive, and set it to Pr.
Page 185
Energy saving operation and energy saving monitor (6) Annual power saving amount, power cost (Pr. 899) By setting the operation time rate [%] (ratio of time when the motor is actually driven by the inverter during a year) in Pr. 899, the annual energy saving effect can be predicted.
Motor noise, EMI measures, mechanical resonance 4.16 Motor noise, EMI measures, mechanical resonance Purpose of Use Parameter that should be Set Refer to Page Reduction of the motor noise Carrier frequency and Measures against EMI and leakage Pr. 72, Pr. 240, Pr. 260 Soft-PWM selection currents Reduce mechanical resonance...
Motor noise, EMI measures, mechanical resonance 4.16.2 Speed smoothing control (Pr. 653) MFVC MFVC MFVC <V/F><GP MFVC> Vibration due to mechanical resonance influences the inverter control, causing the output current (torque) unstable. In this case, the output current (torque) fluctuation can be reduced to ease vibration by changing the output frequency. Parameter Name Initial Value...
Frequency setting by analog input (terminal 2, 4) 4.17 Frequency setting by analog input (terminal 2, 4) Purpose Parameter that should be Set Refer to Page Selection of voltage/current input (terminal 2, 4) Analog input selection Pr. 73, Pr. 267 Perform forward/reverse rotation by analog input.
Page 189
Frequency setting by analog input (terminal 2, 4) NOTE Set Pr. 267 and a voltage/current input switch correctly, then input an analog signal in accordance with the setting. Incorrect setting as in the table below could cause component damage. Incorrect settings other than below can cause abnormal operation.
Page 190
Frequency setting by analog input (terminal 2, 4) Perform operation by analog input selection Inverter The frequency setting signal inputs 0 to 5VDC (or 0 to 10VDC) across Forward rotation the terminals 2 and 5. The 5V (10V) input is the maximum output. The power supply 5V can be input by either using the internal power 0 to 5VDC supply or preparing an external power supply.
Frequency setting by analog input (terminal 2, 4) 4.17.2 Setting the frequency by analog input (voltage input) POINT Switch ON the STF (STR) signal to give a start command. Use the (frequency setting) potentiometer to give a frequency command. [Connection diagram] Inverter (The inverter supplies 5V power to the frequency...
Frequency setting by analog input (terminal 2, 4) REMARKS Pr. 178 STF terminal function selection must be set to "60" (or Pr. 179 STR terminal function selection must be set to "61"). (All are initial values.) The motor will not rotate ... Why? Check that [EXT] is lit.
Frequency setting by analog input (terminal 2, 4) 4.17.4 Bias and gain of frequency setting voltage (current) (Pr. 125, Pr. 126, Pr. 241, C2 (Pr. 902) to C7 (Pr. 905)) You can set the magnitude (slope) of the output frequency as desired in relation to the frequency setting signal (0 to 5VDC, 0 to 10VDC or 4 to 20mADC).
Page 194
Frequency setting by analog input (terminal 2, 4) Change frequency maximum analog input (Pr. 125, Pr. 126) Initial value 60Hz Set Pr. 125 (Pr. 126) when changing frequency setting (gain) of the maximum analog input voltage (current) only. (C2 (Pr. 902) to C7 (Pr.905) setting need not be changed) Gain Pr.
Frequency setting by analog input (terminal 2, 4) 4.17.5 Frequency setting signal (current) bias/gain adjustment method Follow the following procedure to adjust the bias and gain of the frequency setting voltage (current) using the operation panel. Refer to page 188 for the details of parameters. (a) Method to adjust any point by application of a voltage (current) across terminals 2 and 5 (4 and 5).
Page 196
Frequency setting by analog input (terminal 2, 4) (b) Method to adjust any point without application of a voltage (current) across terminals 2 5 (4 (To change from 4V (80%) to 5V (100%)) Operation Display Confirm the operation status indicator and operation mode indicator ...
Page 197
Frequency setting by analog input (terminal 2, 4) (c) Adjusting only the frequency without adjusting the gain voltage (current). (When changing the gain frequency from 60Hz to 50Hz) Operation Display Turn until (Pr. 125) or Terminal 2 input Terminal 4 input is (Pr.
Misoperation prevention and parameter setting restriction 4.18 Misoperation prevention and parameter setting restriction Purpose Parameter that should be Set Refer to Page Limits reset function Reset selection/disconnected PU Trips when PU is disconnected Pr. 75 detection/PU stop selection Stops from PU Prevention of parameter rewrite Parameter write disable selection Pr.
Page 199
Misoperation prevention and parameter setting restriction Disconnected PU detection This function detects that the PU (FR-PU04/FR-PU07) has been disconnected from the inverter for longer than 1s and causes the inverter to provide a fault output (E.PUE) and come to trip. When Pr.
Page 200
Misoperation prevention and parameter setting restriction Restart (PS reset) method when PU stop (PS display) is made during PU operation PU stop (PS display) is made when the motor is stopped from the unit where control command source is not selected (operation panel, parameter unit (FR-PU04/FR-PU07, operation panel for FR-E500 (PA02)) in the PU operation mode.
Misoperation prevention and parameter setting restriction 4.18.2 Parameter write disable selection (Pr. 77) You can select whether write to various parameters can be performed or not. Use this function to prevent parameter values from being rewritten by misoperation. Parameter Name Initial Value Setting Range Description...
Misoperation prevention and parameter setting restriction 4.18.3 Reverse rotation prevention selection (Pr. 78) This function can prevent reverse rotation fault resulting from the incorrect input of the start signal. Parameter Initial Name Setting Range Description Number Value Both forward and reverse rotations allowed Reverse rotation prevention Reverse rotation disabled selection...
Misoperation prevention and parameter setting restriction 4.18.5 Password function (Pr. 296, Pr. 297) Registering a 4-digit password can restrict parameter reading/writing. Parameter Name Initial Value Setting Range Description Number Select restriction level of parameter reading/ 1 to 6, 101 to 106 writing when a password is registered.
Page 204
Misoperation prevention and parameter setting restriction Password lock/unlock (Pr. 296, Pr. 297 ) <Lock> 1) Set parameter reading/writing restriction level.(Pr. 296 9999) Pr. 296 Setting Restriction of Password Pr. 297 Display Unlock Error Value 1 to 6 No restriction Always 0 Displays error count 101 to 106 Restricted at fifth error...
Selection of operation mode and operation location 4.19 Selection of operation mode and operation location Purpose Parameter that should be Set Refer to Page Operation mode selection Operation mode selection Pr. 79 Started in Network operation mode Operation mode at power-on Pr.
Page 206
Selection of operation mode and operation location Operation mode basics The operation mode specifies the source of the start command and the frequency command for the inverter. Basically, there are following operation modes. External operation mode: For inputting start command and frequency command with an external potentiometer and switches which are connected to the control circuit terminal.
Page 207
Selection of operation mode and operation location Operation mode switching method External operation When "0 or 1" is set in Pr. 340 Switching with the PU Switching through the network Press Switch to External the PU to light operation mode through Press the network.
Page 208
Selection of operation mode and operation location Operation mode selection flow In the following flowchart, select the basic parameter setting and terminal connection related to the operation mode. START Connection Parameter setting Operation Where is the start command source? From outside (STF/STR terminal) Where is the frequency command source?
Page 209
Selection of operation mode and operation location External operation mode (setting "0" (initial value), "2") Select the External operation mode when the start command and the frequency command are applied from a frequency setting potentiometer, start switch, etc. which are provided externally and connected to the control circuit terminals of the inverter.
Page 210
Selection of operation mode and operation location PU/External combined operation mode 1 (setting "3") Select the PU/External combined operation mode 1 when applying frequency command from the operation panel or parameter unit (FR-PU04/FR- PU07) and inputting the start command with the external start switch.
Page 211
Selection of operation mode and operation location Switchover mode (setting "6") While continuing operation, you can switch among the PU operation, External operation and Network operation (NET operation). Operation Mode Switching Switching Operation/Operating Status Select the PU operation mode with the operation panel or parameter unit. Rotation direction is the same as that of External operation.
Page 212
Selection of operation mode and operation location NOTE If the X12 (MRS) signal is ON, the operation mode cannot be switched to the PU operation mode when the start signal (STF, STR) is ON. When the MRS signal is used as the PU interlock signal, the MRS signal serves as the normal MRS function (output stop) by turning ON the MRS signal and then changing the Pr.
Page 213
Selection of operation mode and operation location (11) Switching of operation mode by external signals (X65, X66 signals) When Pr. 79 = any of "0, 2, 6", the operation mode switching signals (X65, X66) can be used to change the PU or External operation mode to the Network operation mode during a stop (during a motor stop or start command OFF).
Selection of operation mode and operation location 4.19.2 Setting the frequency by the operation panel POINT Use the operation panel to give a start command and a frequency command. (PU operation) Operation panel Operation Operate at 30Hz. example Operation Display Screen at power-ON The monitor display appears.
Page 215
Selection of operation mode and operation location REMARKS Operation cannot be performed at the set frequency ... Why? Did you carry out step 4 within 5s after step 3? (Did you press within 5s after turning The frequency does not change by turning ...
Selection of operation mode and operation location 4.19.3 Setting the frequency by the operation panel (Pr. 79 = 3) POINT Switch ON the STF(STR) signal to give a start command. Use the operation panel ( ) to give a frequency command. ...
Selection of operation mode and operation location 4.19.4 Setting the frequency by analog input (voltage input) POINT Use the operation panel ( to give a start command. Use the potentiometer (by connecting terminal 2 and 5) to give a frequentry command. ...
Selection of operation mode and operation location 4.19.5 Operation mode at power-ON (Pr. 79, Pr. 340) When power is switched ON or when power comes back ON after instantaneous power failure, the inverter can be started up in the Network operation mode. After the inverter has started up in the Network operation mode, parameter write and operation can be performed from a program.
Selection of operation mode and operation location 4.19.6 Start command source and frequency command source during communication operation (Pr. 338, Pr. 339, Pr. 551) When the RS-485 communication with the PU connector is used, the external start command and frequency command can be valid.
Page 220
Selection of operation mode and operation location Controllability through communication Controllability through communication in each operation mode is shown below. Monitoring and parameter read can be performed from any operation regardless of operation mode. Operation External/PU External/PU Mode Operation Condition External Combined Combined...
Page 221
Selection of operation mode and operation location Selection of control source in Network operation mode (Pr. 338, Pr. 339) There are two control sources: start command source, which controls the signals related to the inverter start command and function selection, and speed command source, which controls signals related to frequency setting. In Network operation mode, the commands from the external terminals and communication are as listed below.
Page 222
Selection of operation mode and operation location Switching of command source by external signal (X67) In the Network operation mode, the command source switching signal (X67) can be used to switch the start command source and speed command source. Set "67" to any of Pr. 178 to Pr. 182 (input terminal function selection) to assign the X67 signal to the control terminal. When the X67 signal is OFF, the start command source and speed command source are control terminal.
Pins No. 2 and 8 provide power to the parameter unit. Do not use these pins for RS-485 communication. When making RS-485 communication among the FR-F700PJ, FR-E500, FR-S500 and F500J series, incorrect connection of pins No.2 and 8 (parameter unit power supply) of the above PU connector may result in the inverter malfunction or failure.
Page 224
Communication operation and setting PU connector communication system configuration Connection of a computer to the inverter (1:1 connection) Station 0 Station 0 Computer Computer Inverter Inverter Inverter RS-232C connector FR-PU07 RS-485 RS-232C connector Maximum connector connector interface/terminals cable RS-232C RS-485 RJ-45 connector 2) converter RJ-45...
Page 225
Do not use pins No. 2, 8 of the communication cable. (Refer to page 218) When making RS-485 communication among the FR-F700PJ, FR-E500, FR-S500, and FR-F500J series, incorrect connection of pins No.2 and 8 (parameter unit power supply) of the above PU connector may result in the inverter malfunction or failure.
Communication operation and setting 4.20.2 Initial settings and specifications of RS-485 communication (Pr. 117 to Pr. 120, Pr. 123, Pr. 124, Pr. 549) The following parameters are used to perform required settings for RS-485 communication between the inverter and personal computer. ...
Communication operation and setting 4.20.3 Operation selection at communication error occurrence (Pr. 121, Pr. 122, Pr. 502, Pr. 779) You can select the inverter operation when a communication line error occurs during RS-485 communication from the PU connector. Parameter Initial Setting Name Description...
Page 228
Communication operation and setting REMARKS Pr. 121 is valid only when Mitsubishi inverter (computer link operation) protocol is selected. Pr. 121 is not valid when Modbus- RTU communication protocol is selected. How the inverter operates at a communication error differs according to the Pr. 502 Stop mode selection at communication error setting.
Page 229
Communication operation and setting Stop operation selection at occurrence of communication fault (Pr. 502) Stop operation when retry count exceeds (Mitsubishi inverter protocol only) or signal loss detection error occurs can be selected. Operation at fault occurrence Pr. 502 Setting Operation Indication Fault Output...
Communication operation and setting REMARKS The fault output indicates fault output signal (ALM signal) or alarm bit output. When the setting was made to provide a fault output, the fault description is stored into the faults history. (The fault description is written to the faults history when a fault output is provided.) When no fault output is provided, the fault record overwrites the fault indication of the faults history temporarily, but is not stored.
Communication operation and setting 4.20.5 Mitsubishi inverter protocol (computer link communication) You can perform parameter setting, monitoring, etc. from the PU connector of the inverter using the Mitsubishi inverter protocol (computer link communication). Communication The communication specifications are given below. Related Item Description...
Page 232
Communication operation and setting Communication operation presence/absence and data format types Data communication between the computer and inverter is made in ASCII code (hexadecimal code). Communication operation presence/absence and data format types are as follows: Operation Multi Parameter Inverter Parameter Operation Monitor Command...
Page 233
Communication operation and setting Data reading format Communication request data from the computer to the inverter 1) Number of Characters Format Inverter Instruction code station number check Reply data from the inverter to the computer 3) (No data error detected) Number of Characters Format Inverter...
Page 234
Communication operation and setting Data definitions 1) Control code Signal ASCII Code Description Start of Text (Start of data) End of Text (End of data) Enquiry (Communication request) Acknowledge (No data error detected) Line Feed Carriage Return Negative Acknowledge (Data error detected) 2) Inverter station number Specify the station number of the inverter which communicates with the computer.
Page 235
Communication operation and setting 7) Error code If any error is found in the data received by the inverter, its definition is sent back to the computer together with the NAK code. Error Error Item Error Description Inverter Operation Code The number of errors detected consecutively in communication request Computer NAK error data from the computer is greater than allowed number of retries.
Page 236
Communication operation and setting Instructions for the program 1) When data from the computer has any error, the inverter does not accept that data. Hence, in the user program, always insert a retry program for data error. 2) All data communication, for example, run command or monitoring, are started when the computer gives a communication request.
Page 237
Communication operation and setting General flowchart Port open Communication setting Time out setting Send data processing Data setting Sum code calculation Data transmission Receive data waiting Receive data processing Data retrieval Screen display CAUTION Always set the communication check time interval before starting operation to prevent hazardous conditions. Data communication is not started automatically but is made only once when the computer provides a communication request.
Page 238
Communication operation and setting Setting items and set data After completion of parameter settings, set the instruction codes and data then start communication from the computer to allow various types of operation control and monitoring. Number of Read/ Instruction Item Data Definition Data Digits Write...
Page 239
Communication operation and setting Number of Instruction Read/ Item Data Definition Data Digits Write Code (Format) Fault history batch 4 digits Write H9696: Clears the fault history as a batch clear (A, C/D) All parameters return to the initial values. Whether to clear communication parameters or not can be selected according to data.
Page 240
Communication operation and setting Example) When reading the C3 (Pr. 902) and C6 (Pr. 904) settings from the inverter of station 0 Computer Send Data Inverter Send Data Description ENQ 00 FF 0 01 82 ACK 00 Set "H01" to the extended link parameter. ENQ 00 EC 0 01 7E ACK 00 Set "H01"...
Communication operation and setting [Fault data] Refer to page 297 for details of fault description Fault record display example (instruction code H74) Data Definition Data Definition Data Definition For read data H3010 No fault E.UVT E.RET (Previous fault ..THT) E.ILF E.CPU present...
Page 242
Communication operation and setting [Multi command (HF0)] Sending data format from computer to inverter Number of Characters Format Send Receive Inverter Instruction Data2 Waiting data data station Code Data1 CR/LF time check number (HF0) type type Reply data format from inverter to computer (No data error detected) Number of Characters Format...
Communication operation and setting 4.20.6 Modbus-RTU communication specifications (Pr. 117, Pr. 118, Pr. 120, Pr. 122, Pr. 343, Pr. 502, Pr. 549, Pr. 779) Using the Modbus-RTU communication protocol, communication operation or parameter setting can be performed from the PU connector of the inverter. Parameter Setting Name...
Page 244
Communication operation and setting Communication specification The communication specifications are given below. Related Item Description Parameter Communication protocol Modbus-RTU protocol Pr. 549 Conforming standard EIA-485(RS-485) — Number of connectable devices 1:N (maximum 32 units), setting is 0 to 247 stations Pr.
Page 245
Communication operation and setting Message format Inverter response time Query communication (Refer to the following table for the data check time) Programmable controller (master) Query message Response message Inverter (slave) Data absence time (3.5 bytes or more) Broadcast communication Query message Programmable controller (master) No Response Inverter (slave)
Page 246
Communication operation and setting Message frame (protocol) Communication method Basically, the master sends a query message (question) and the slave returns a response message (response). When communication is normal, Device Address and Function Code are copied, and when communication is abnormal (function code or data code is illegal), bit 7 (= 80h) of Function Code is turned ON and the error code is set to Data Bytes.
Page 247
Communication operation and setting Message format types The message formats corresponding to the function codes in Table 1 on page 241 will be explained. Read holding register data (H03 or 03) Can read the description of 1) system environment variables, 2) real-time monitor, 3) faults history, and 4) inverter parameters assigned to the holding register area (refer to the register list (page 247)) Query message 1) Slave...
Page 248
Communication operation and setting Write holding register data (H06 or 06) Can write the description of 1) system environment variables and 4) inverter parameters assigned to the holding register area (refer to the register list ( page 247)). Query message 1) Slave Address 2) Function 3) Register Address...
Page 249
Communication operation and setting Function diagnosis (H08 or 08) A communication check can be made since the query message sent is returned unchanged as a response message (function of sub function code H00). Sub function code H00 (Return Query Data) Query message 1) Slave Address 2) Function...
Page 250
Communication operation and setting Description of normal response 1) to 4) (including CRC check) of the normal response are the same as those of the query message. Example: To write 0.5s (H05) to 41007 (Pr. 7) at the slave address 25 (H19) and 1s (H0A) to 41008 (Pr. 8). Query message Slave Starting...
Page 251
Communication operation and setting Error response An error response is returned if the query message received from the master has an illegal function, address or data. No response is returned for a parity, CRC, overrun, framing or busy error. NOTE No response message is sent in the case of broadcast communication also.
Page 252
Communication operation and setting Modbus registers System environment variable Register Definition Read/write Remarks 40002 Inverter reset Write Any value can be written. 40003 Parameter clear Write Set H965A as a written value. 40004 All parameter clear Write Set H99AA as a written value. 40006 Parameter clear...
Page 253
Communication operation and setting Parameter Read/ Parameter Register Parameter Name Remarks Write 41000 to Refer to the parameter list (page The parameter number + 41000 is the register 0 to 999 Read/write 41999 64) for the parameter names. number. Terminal 2 frequency setting C2(902) 41902...
Page 254
Communication operation and setting Fault code list Data Definition Data Definition Data Definition No fault E.UVT E.RET E.ILF E.CPU present E.OLT E.CDO E.OC1 E.SOT E.IOH E.OC2 E.BE E.AIE E.OC3 E.GF E.SAF E.OV1 E.LF E.OS E.OV2 E.OHT E.PID E.OV3 E.PTC E.THT E.PE E.THM E.PUE...
Special operation and frequency control 4.21 Special operation and frequency control Purpose Parameter that should be Set Refer to Page Perform process control such as Pr. 127 to Pr. 134, Pr. 553, Pr. 554, PID control pump and air volume. Pr.
Page 256
Special operation and frequency control Parameter Initial Setting Name Description Number Value Range 0 to PID display bias Set the coefficient on bias (minimum) side of terminal 4 input. 9999 500.00 (934) coefficient 9999 Displayed in %. PID display bias 0 to Set the converted % on bias (minimum) side current /voltage of terminal (934)
Page 257
Special operation and frequency control PID control basic configuration Pr. 128 = "20, 21" (measured value input) Inverter circuit Motor Pr. 133 Manipulated PID operation or terminal 2 variable Kp 1+ Set point 0 to 5VDC (0 to 10VDC) Terminal 4 Feedback signal (measured value) 4 to 20mADC (0 to 5V, 0 to 10V) Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time...
Page 258
Special operation and frequency control 4)Reverse operation Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is positive, and decreases the manipulated variable if deviation is negative. Deviation Set point [Heating] X>0 Cold Increase Set point X<0 Decrease...
Special operation and frequency control I/O signals and parameter setting Set "20, 21" in Pr. 128 to perform PID operation. Set "14" in any of Pr. 178 to Pr. 182 (input terminal function selection) to assign PID control selection signal (X14) to turn the X14 signal ON.
Page 260
Special operation and frequency control NOTE Changing the terminal function using any of Pr. 178 to Pr. 182, Pr. 190 and Pr. 192 may affect the other functions. Set parameters after confirming the function of each terminal. When the Pr. 267 setting was changed, check the voltage/current input switch setting. Different setting may cause a fault, failure or malfunction.
Page 261
Special operation and frequency control PID output suspension function (SLEEP function) (SLEEP signal, Pr. 575 to Pr. 577 ) The inverter stops operation if the output frequency after PID operation remains at less than the Pr. 576 Output interruption detection level setting for longer than the time set in Pr. 575 Output interruption detection time. This function can reduce energy consumption in the low-efficiency, low-speed range.
Page 262
Special operation and frequency control PID monitor function The PID control set point, measured value and deviation value can be displayed on the operation panel and output from the terminal FM. In the deviation monitor, a negative percent can be displayed as an integer, like 0% as 1000 and so on. (The deviation monitor cannot be output from the terminal FM.) For each monitor, set the following value in Pr.
Page 263
Special operation and frequency control (10) Calibration example (A detector of 4mA at 0C and 20mA at 50C is used to adjust the room temperature to 25C under PID control. The set point is given to across inverter terminals 2-5 (0 to 5V).) Start Determination of set point Set the room temperature to 25 C.
Page 264
Special operation and frequency control <Set point input calibration> 1) Setting with terminal 2 input 1. Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5. 2. Enter in C2 (Pr. 902) the frequency which should be output by the inverter at the deviation of 0% (e.g. 0Hz). 3.
Page 265
Special operation and frequency control NOTE If the multi-speed (RH, RM, RL, REX signal) or Jog operation (JOG signal) is entered with the X14 signal ON, PID control is stopped and multi-speed or Jog operation is started. If the setting is as follows, PID control becomes invalid. Pr.
Page 266
Special operation and frequency control Take caution when the following condition is satisfied because the inverter recognizes the deviation value as a negative (positive) value even though a positive (negative) deviation is given: Pr. 934 PID display bias coefficient Pr.
Special operation and frequency control 4.21.2 Regeneration avoidance function (Pr. 665, Pr. 882, Pr. 883, Pr. 885, Pr. 886) This function detects a regeneration status and increases the frequency to avoid the regenerative status. Possible to avoid regeneration by automatically increasing the frequency to continue operation if the fan happens to rotate faster than the set speed due to the effect of another fan in the same duct.
Page 268
Special operation and frequency control REMARKS The acceleration/deceleration ramp while the regeneration avoidance function is operating changes depending on the regeneration load. The DC bus voltage of the inverter is about times of normal input voltage. (However, it varies with the input power supply waveform.) When the input voltage is 220VAC, bus voltage is approximately 311VDC.
Useful functions 4.22 Useful functions Purpose Parameter that should be Set Refer to Page Cooling fan operation To increase cooling fan life Pr. 244 selection Inverter part life display Pr. 255 to Pr. 259 Maintenance output To determine the maintenance time Pr.
Useful functions 4.22.2 Display of the lives of the inverter parts (Pr. 255 to Pr. 259) Degrees of deterioration of main circuit capacitor, control circuit capacitor, cooling fan and inrush current limit circuit can be diagnosed by a monitor. When any part has approached to the end of its life, an alarm can be output by self diagnosis to prevent a fault. (Use the life check of this function as a guideline since the life except the main circuit capacitor is calculated theoretically.) For the life check of the main circuit capacitor, the alarm signal (Y90) will not be output if a measuring method of (4) is...
Page 271
Useful functions Life alarm display and signal output (Y90 signal, Pr. 255) Whether any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush current limit circuit has reached the life alarm output level or not can be checked by Pr. 255 Life alarm status display and life alarm signal (Y90). 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 Pr.
Page 272
Useful functions Main circuit capacitor life display (Pr. 258, Pr. 259) The deterioration degree of the control circuit capacitor is displayed in Pr. 258 as a life. On the assumption that the main circuit capacitor capacitance at factory shipment is 100%, the capacitor life is displayed in Pr.
Useful functions 4.22.3 Maintenance timer alarm (Pr. 503, Pr. 504) When the cumulative energization time of the inverter reaches the parameter set time, the maintenance timer output signal (Y95) is output. (MT) is displayed on the operation panel. This can be used as a guideline for the maintenance time of peripheral devices. Parameter Name Initial Value...
Useful functions 4.22.4 Current average value monitor signal (Pr. 555 to Pr. 557) The average value of the output current during Programmable controller constant speed operation and the maintenance timer Output unit Input unit value are output as a pulse to the current average Inverter value monitor signal (Y93).
Page 275
Useful functions 3) Setting of Pr.557 Current average value monitor signal output reference current Set the reference (100%) for outputting the signal of the current average value. Obtain the time to output the signal from the following calculation. Output current average value ...
Useful functions 4.22.5 Free parameter (Pr. 888, Pr. 889) You can input any number within the setting range of 0 to 9999. For example, the number can be used: As a unit number when multiple units are used. As a pattern number for each operation application when multiple units are used. ...
Useful functions 4.22.6 Initiating a fault (Pr.997) A fault is initiated by setting the parameter. This function is useful to check how the system operates at a fault. Parameter Name Initial value Setting range Description number 16 to 18, 32 to 34, 48, 49, The setting range is same with the one for 64, 81, 82, 96, 97, 112, fault data codes of the inverter (which can...
Useful functions 4.22.7 Setting multiple parameters as a batch (Pr.999) Parameter settings are changed as a batch. Those include communication parameter settings for the Mitsubishi human machine interface (GOT) connection and rated frequency settings of 50Hz/60Hz. Multiple parameters are changed automatically. Users do not have to consider each parameter number. (Parameter setting mode) Parameter Name...
Page 279
Useful functions (2) Automatic parameter setting using the operation panel (parameter setting mode) The communication setting parameters for the GOT connection with a PU connector are Operation example automatically set. Operation Display Screen at power-ON The monitor display appears. PU indicator is lit. Press to choose the PU operation mode.
Page 280
Useful functions (3) Parameter setting mode (Lit) <Automatic parameter setting mode> Always displayed as "0" when the parameter is read. Write "1" to select the automatic setting. Pressing in the "0" setting displays the next Pr. (Lit) Example Example Flickers...
Page 281
Useful functions (4) List of automatically-set parameters The following tables show which parameters are changed in each of the automatic parameter settings. NOTE If the automatic setting is performed with Pr.999 or the parameter setting mode, the listed settings including the changed parameter settings (changed from the initial setting) will be automatically changed.
Setting the parameter unit and operation panel 4.23 Setting the parameter unit and operation panel Purpose Parameter that should be Set Refer to Page Selection of rotation direction by RUN key rotation Pr. 40 direction selection of the operation panel Switch the display language of the PU display language Pr.
Setting the parameter unit and operation panel 4.23.3 Setting dial potentiometer mode/key lock selection (Pr. 161) The setting dial of the operation panel can be used for setting like a potentiometer. The key operation of the operation panel can be disabled. Parameter Setting Name...
Page 284
Setting the parameter unit and operation panel Using the setting dial like a potentiometer to set the frequency Operation example Change the frequency from 0Hz to 60Hz during operation Operation Display 1. Screen at power-ON The monitor display appears. PU indicator is lit. Press to choose the PU operation mode.
Page 285
Setting the parameter unit and operation panel Disable the setting dial and key operation of the operation panel (Press [MODE] long (2s)) Operation using the setting dial and key of the operation panel can be invalid to prevent parameter change, and unexpected start or frequency setting.
Setting the parameter unit and operation panel 4.23.4 Magnitude of frequency change setting (Pr. 295) When setting the set frequency with the setting dial, frequency changes in 0.01Hz increments in the initial status. Setting this parameter increases the magnitude of frequency which changes according to the rotated amount of the setting dial, improving operability.
Setting the parameter unit and operation panel 4.23.5 Buzzer control (Pr. 990) You can make the buzzer "beep" when you press the key of the parameter unit (FR-PU04/FR-PU07). Parameter Name Initial Value Setting Range Description Number Without buzzer PU buzzer control With buzzer The above parameter can be set when Pr.
FR-E500 series operation panel (PA02) setting 4.24 FR-E500 series operation panel (PA02) setting The operation panel (PA02) for the FR-E500 series can be hooked up with the PU cable for use. (The inverter can not be directly connected.) Purpose Parameter that should be Set Refer to Page Select the frequency setting method Frequency setting...
FR-E500 series operation panel (PA02) setting 4.24.2 Bias and gain of the built-in frequency setting potentiometer (C22 (Pr. 922) to C25 (Pr. 923)) When the operation panel (PA02) for the FR-E500 series is hooked up with the PU cable, the magnitude (slope) of the output frequency to the frequency setting potentiometer of the operation panel can be set as desired.
Page 290
FR-E500 series operation panel (PA02) setting Pr. 923 "Built-in frequency setting potentiometer gain" (Pr. 922 can be adjusted in a similar manner.) Set the magnitude (slope) of the output frequency by the built-in potentiometer as desired using the built-in frequency setting potentiometer.
Page 291
FR-E500 series operation panel (PA02) setting Operation Set the gain frequency in Pr.923 to display the analog voltage value of the built-in frequency setting potentiometer in %. (80Hz maximum) Current setting of gain Changing the gain frequency frequency Press to change the set frequency. Press for 1.5s Analog voltage value (%) of the built-in A near-0 value is shown at the...
Page 292
FR-E500 series operation panel (PA02) setting Method to adjust any point without turning the potentiometer (changing from 4V(80%) to 5V(100%)) Operation Perform steps 1. to 4. on page 285, 286. Set the gain voltage (%). Analog voltage Press the Set the gain voltage (%) with value (%) of the key once to display...
Page 293
FR-E500 series operation panel (PA02) setting [Setting with the inverter operation panel without fitting the FR-E500 series operation panel (PA02)] (a) Method to adjust any point (to change to 80% from 100%) Operation Display Confirm the operation status indicator and operation mode indicator ...
Page 294
1.5s. Past four faults are stored in the faults history when the operation panel PA02 is connected. All faults (E.ILF, E.IOH. E.AIE, E.CDO, E.PTC, E.SOT, E.PID, E.SAF) added to the FR-F700PJ series are displayed as E.14.
Parameter clear/ All parameter clear 4.25 Parameter clear/ All parameter clear POINT Set "1" in Pr.CL Parameter clear, ALLC all parameter clear to initialize all parameters. (Parameters are not cleared when "1" is set in Pr. 77 Parameter write selection.) ...
Initial value change list 4.26 Initial value change list Displays and sets the parameters changed from the initial value. Operation Display Screen at power-ON The monitor display appears. PU indicator is lit. Press to choose the PU operation mode. PRM indicator is lit. Press to choose the parameter setting mode.
Check and clear of the faults history 4.27 Check and clear of the faults history Check for the faults history Monitor/frequency setting Parameter setting [Operation panel is [Parameter setting change] used for operation] Faults history [Operation for displaying the faults history] Past eight faults can be displayed with the setting dial.
Page 298
Check and clear of the faults history Clearing procedure POINT Set "1" in Er.CL Fault history clear to clear the faults history. Operation Display Screen at power-ON The monitor display appears. PRM indicator is lit. Press to choose the parameter setting mode. (The parameter number read previously appears.) Turn...
TROUBLESHOOTING This chapter provides the "TROUBLESHOOTING" of this product. Always read the instructions before using the equipment. Reset method of protective function ......... 296 List of fault or alarm indications ..........297 Causes and corrective actions ........... 298 Correspondences between digital and actual characters ..308 Check first when you have a trouble .........
Reset method of protective function When a fault occurs in the inverter, the inverter trips and the PU display automatically changes to one of the following fault or alarm indications. If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales representative.
List of fault or alarm indications List of fault or alarm indications Fault Refer Fault Refer Operation Panel Operation Panel Name data Name data Indication Indication code Page code Page E.FIN Heatsink overheat E--- Faults history — (H40) E.UVT HOLD Operation panel lock —...
Causes and corrective actions Causes and corrective actions (1) Error message A message regarding operational troubles is displayed. Output is not shut off. Operation panel HOLD indication Name Operation panel lock Description Operation lock mode is set. Operation other than is invalid.
Page 304
Causes and corrective actions Operation panel Err. indication Name Inverter reset Executing reset using RES signal, or reset command from communication or PU Description Displays at powering OFF. Corrective action Turn OFF the reset command (2) Warning When a warning occurs, the output is not shut off.
Page 305
Causes and corrective actions Operation panel FR-PU04 indication FR-PU07 Name PU stop Stop with of the PU is set in Pr. 75 Reset selection/disconnected PU detection/PU stop selection. (For Pr. 75 refer to Description page 193 .) Check point Check for a stop made by pressing of the operation panel.
Page 306
Causes and corrective actions Operation panel FR-PU04 —— indication FR-PU07 Name Description Appears when the shorting wire across the terminals S1 and SC or the terminals S2 and SC is disconnected. Check point Check if the shorting wire across the terminals S1 and SC or the terminals S2 and SC is disconnected. Corrective action Short across the terminals S1 and SC and the terminals S2 and SC with shortening wires.
Page 307
Causes and corrective actions Operation panel FR-PU04 E.OC2 Stedy Spd OC indication FR-PU07 Name Overcurrent trip during constant speed When the inverter output current reaches or exceeds approximately 170% of the rated current during constant speed Description operation, the protective circuit is activated and the inverter trips. ...
Page 308
Causes and corrective actions Operation panel FR-PU04 Stedy Spd OV E.OV2 indication FR-PU07 Name Regenerative overvoltage trip during constant speed If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value, Description the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage produced in the power supply system.
Page 309
Causes and corrective actions Operation panel FR-PU04 E.FIN H/Sink O/Temp indication FR-PU07 Name Heatsink overheat If the heatsink overheats, the temperature sensor is actuated and the inverter trips. The FIN signal can be output when the temperature becomes approximately 85% of the heatsink overheat protection Description operation temperature.
Page 310
Causes and corrective actions Operation panel FR-PU04 E.BE Br. Cct. Fault indication FR-PU07 Name Brake transistor alarm detection When a brake transistor alarm has occurred due to the large regenerative energy from the motor etc., the brake transistor alarm is detected and the inverter trips. Description In this case, the inverter must be powered OFF immediately.
Page 311
Causes and corrective actions Operation panel FR-PU04 E.PE Corrupt Memry indication FR-PU07 Name Parameter storage device fault (control circuit board) Description Appears when a fault occurred in the stored parameters. (EEPROM fault) Check point Check for too many number of parameter write times. Please contact your sales representative.
Page 312
Causes and corrective actions Operation panel FR-PU04 Fault 14 E.AIE FR-PU07 Analog in error indication Name Analog input fault Appears if voltage(current) is input to terminal 4 when the setting in Pr.267 Terminal 4 input selection and the setting of Description voltage/current input switch are different.
Correspondences between digital and actual characters Correspondences between digital and actual characters There are the following correspondences between the actual alphanumeric characters and the digital characters displayed on the operation panel: Actual Digital Actual Digital Actual Digital...
Check first when you have a trouble Check first when you have a trouble POINT If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then set the required parameter values and check again. 5.5.1 Motor does not start Refer...
Page 315
Check first when you have a trouble Refer Check Possible Cause Countermeasures points page Increase Pr. 0 setting by 0.5% increments while Pr. 0 Torque boost setting is improper when V/F control is observing the rotation of a motor. used. If that makes no difference, decrease the setting.
Check first when you have a trouble 5.5.2 Motor or machine is making abnormal acoustic noise Refer Check Possible Cause Countermeasures points page Input Take countermeasures against EMI. signal Disturbance due to EMI when frequency command is Parameter given from analog input (terminal 2, 4). Increase the Pr.
Check first when you have a trouble 5.5.3 Inverter generates abnormal noise Refer Check Possible Cause Countermeasures points page Install the fan cover correctly. Fan cover was not correctly installed when a cooling fan Install the fan cover securely with the enclosed fan cover was replaced.
Check first when you have a trouble 5.5.7 Acceleration/deceleration is not smooth Refer Check Possible Cause Countermeasures points page Acceleration/deceleration time is too short. Increase acceleration/deceleration time. Torque boost (Pr. 0, Pr. 46) setting is improper under V/F Increase/decrease Pr. 0 Torque boost setting value by control, so the stall prevention function is activated.
Check first when you have a trouble 5.5.9 Operation mode is not changed properly Refer Check Possible Cause Countermeasures points page Check that the STF and STR signals are OFF. Input Start signal (STF or STR) is ON. When either is ON, the operation mode cannot be signal changed.
Check first when you have a trouble 5.5.12 Speed does not accelerate Refer Check Possible Cause Countermeasures points page Check if the start command and the frequency Start command and frequency command are chattering. — command are correct. Input The wiring length used for analog frequency command Perform analog input bias/gain calibration.
Page 322
PRECAUTIONS FOR MAINTENANCE AND INSPECTION This chapter provides the "PRECAUTIONS FOR MAINTENANCE AND INSPECTION" of this product. Always read the instructions before using the equipment. Inspection items................318 Measurement of main circuit voltages, currents and powers ..324...
Inspection items The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors.
Inspection items 6.1.4 Display of the life of the inverter parts The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan and each parts of the inrush current limit circuit is near its end. It gives an indication of replacement time. The life alarm output can be used as a guideline for life judgement.
Inspection items 6.1.7 Replacement of parts The inverter consists of many electronic parts such as semiconductor devices. The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically. Use the life check function as a guidance of parts replacement.
Page 327
Inspection items Reinstallation 1) After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" faces up. AIR FLOW <Fan side face> 2) Reconnect the fan connectors. 3) When wiring, avoid the cables being caught by the fan. 5.5K or higher 3.7K or lower 4) Reinstall the fan cover.
Page 328
Inspection items Smoothing capacitors A large-capacity aluminum electrolytic capacitor is used for smoothing in the main circuit DC section, and an aluminum electrolytic capacitor is used for stabilizing the control power in the control circuit. Their characteristics are deteriorated by the adverse effects of ripple currents, etc.
Measurement of main circuit voltages, currents and powers Measurement of main circuit voltages, currents and powers Since the voltages and currents on the inverter power supply and output sides include harmonics, measurement data depends on the instruments used and circuits measured. When instruments for commercial frequency are used for measurement, measure the following circuits with the instruments given on the next page.
Page 330
Measurement of main circuit voltages, currents and powers Measuring Points and Instruments Item Measuring Point Measuring Instrument Remarks (Reference Measured Value) R/L1 and S/L2 Commercial power supply Power supply voltage Moving-iron type AC S/L2 and T/L3 Within permissible AC voltage fluctuation (Refer to voltmeter...
Measurement of main circuit voltages, currents and powers 6.2.1 Measurement of powers Use digital power meters (for inverter) for the both of inverter input and output side. Alternatively, measure using electrodynamic type single-phase wattmeters for the both of inverter input and output side in two-wattmeter or three- wattmeter method.
Measurement of main circuit voltages, currents and powers 6.2.3 Measurement of currents Use moving-iron type meters on both the input and output sides of the inverter. However, If the carrier frequency exceeds 5kHz, do not use that meter since an overcurrent losses produced in the internal metal parts of the meter will increase and the meter may burn out.
Measurement of main circuit voltages, currents and powers 6.2.8 Insulation resistance test using megger For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test on the control circuit. (Use a 500VDC megger.) Motor R/L1 Power...
SPECIFICATIONS This chapter provides the "SPECIFICATIONS" of this product. Always read the instructions before using the equipment. Rating..................... 330 Common specifications ............... 331 Outline dimension drawings............333 Specification of the premium high-efficiency IPM motor [MM- EFS (1500r/min) series] ..............339 Specification of dedicated IPM motor [MM-EF(1800r/min) series] ....................
Common specifications Common specifications High carrier frequency PWM control (V/F control)/Optimum excitation control/General-purpose magnetic flux vector Control method control/IPM motor control Output frequency range 0.2 to 400Hz 0.06Hz/60Hz (terminals 2 and 4: 0 to 10V/10-bit) Frequency setting Analog input 0.12Hz/60Hz (terminals 2 and 4: 0 to 5V/9-bit) resolution 0.06Hz/60Hz (terminal 4: 0 to 20mA/10-bit) Digital input...
Page 337
Common specifications Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal operation, motor protection thermal operation, heatsink overheat, undervoltage , input phase loss , output side Protective earth (ground) fault overcurrent at start , output phase loss, external thermal relay operation , PTC thermistor function...
Specification of the premium high-efficiency IPM motor [MM-EFS (1500r/min) Specification of the premium high-efficiency IPM motor [MM- EFS (1500r/min) series] 7.4.1 Motor specification 200V class MM-EFS Motor model 400V class MM-EFS 200V class Compatible FR-F720PJ- 0.75 400V class inverter FR-F740PJ- ...
Specification of dedicated IPM motor [MM-EF(1800r/min) series] Specification of dedicated IPM motor [MM-EF(1800r/min) series] 7.5.1 Motor specification 200V class MM-EF2 Motor model 400V class MM-EF24 200V class FR-F720PJ-K Compatible 0.75 inverter 400V class FR-F740PJ-K Rated output 0.75 (kW) Continuous characteristic Rated torque ...
User initial value list and user clear of the HELP function can not be used. 2) For the FR-F700PJ series, many protective functions have been added. These functions activate, but all faults are displayed as "Fault 14". When the faults history has been checked, "E.14" appears. Added faults display will not appear on the parameter unit.
Page 348
Item FR-F500J FR-F700PJ Parameter Parameter Name Name Number Number Pr. 17 RUN key rotation direction selection Pr. 40 RUN key rotation direction selection Pr. 21 Stall prevention function selection Pr. 156 Stall prevention operation selection Stall prevention operation reduction Stall prevention operation reduction Pr.
Appendix 2 Options and products available on the market Applicable Name Model Applications, Specifications, etc. Inverter Parameter unit FR-PU07 Applicable for all Interactive parameter unit with LCD display (Eight languages) FR-PU04 models Enclosure surface operation This operation panel enables inverter operation and monitoring Applicable for all FR-PA07 of frequency, etc.
Page 350
Applicable Name Model Applications, Specifications, etc. Inverter For independent operation. With frequency meter, frequency Manual controller FR-AX potentiometer and start switch. For synchronous operation (1.5VA) by external signal (0 to 5V, DC tach. follower FR-AL 0 to 10V DC) For three speed switching, among high, middle and low speed Three speed selector FR-AT...
Appendix 3 Specification change Check the SERIAL number indicated on the inverter rating plate or package. For how to find the SERIAL number, refer to page Changed functions The following functions are available for the inverters manufactured in October 2012 or later. Item Changed functions MM-EFS compatibility...
Appendix 4 Index Numerics DC injection brake of IPM motor control (Pr.10, Pr.11)..130 Detection of output frequency 15-speed selection (REX signal) ........106, 134 (SU, FU signal, Pr. 41 to Pr. 43) ........144 Display of the life of the inverter parts (Pr.
Page 353
Insulation resistance test using megger .......327 Output current..............152, 157 Inverter I/O Terminal Monitor..........152, 155 Output current detection (Y12 signal) ......140, 146 Inverter installation environment ..........9 Output current detection function (Y12 signal, Y13 signal, Pr. Inverter operation ready (RY signal) ......140, 142 150 to Pr.
Page 354
Regenerative brake duty..........131, 152 Regenerative brake prealarm (RB) ....... 131, 300 Zero current detection (Y13 signal) .......140, 146 Regenerative brake prealarm (RBP signal)....131, 140 Regenerative overvoltage trip during acceleration (E.OV1)................262, 302 Regenerative overvoltage trip during constant speed (E.OV2)................
Page 355
REVISIONS *The manual number is given on the bottom left of the back cover. Manual Number Print Date Revision Mar. 2011 IB(NA)-0600426ENG-A First edition Mar. 2013 IB(NA)-0600426ENG-B Addition MM-EFS compatibility Pr. 154 Voltage reduction selection during stall prevention operation ...
Page 356
HEAD OFFICE: TOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN IB(NA)-0600426ENG-B (1303)MEE Printed in Japan Specifications subject to change without notice.