Inverter placement (Installation of Filterpack)
NOTE
When encasing multiple inverters, install them in parallel as a cooling
measure.
Install the inverter vertically.
For heat dissipation and maintenance, allow minimum clearance shown
in the figures below from the inverter to the other devices and to the
inner surface of the enclosure.
5cm
Measurement
position
-10 C to +50 C
(non-freezing)

Allow 5cm or more clearance for 5.5K or higher.

When using the inverters at the surrounding air temperature of 40C or less, the inverters can be installed without any clearance between
them (0cm clearance).
1.5.2

Installation of the inverter and Filterpack (for rear panel installation)

<0.4K to 3.7K>
Remove the front cover and wiring cover to attach the inverter.
FR-F720PJ-0.4K to 0.75K
Screw for inverter rear
panel installation
Front cover
<5.5K to 15K>
Remove the L-bracket installation screws from Filterpack (two for the 7.5K or lower, three for the 11K or higher), and attach
the included L-bracket to Filterpack with these screws.
Remove the front cover to attach the inverter.
L-bracket installation screw
Screw for inverter
rear panel installation
12
Measurement
10cm or more
position
5cm
1cm or
1cm or
∗1, ∗2
5cm
more
more
10cm or more
Screw for inverter rear
panel installation
Wiring cover
1cm or
∗1, ∗2
∗1
more
FR-F720PJ-1.5K to 3.7K
FR-F740PJ-0.4K to 3.7K
Screw for inverter rear
panel installation
Front cover
Rear panel installation L-bracket
Screw for inverter rear
panel installation
Wiring cover
Screw for inverter rear panel installation