Energy Saving Monitor (Pr. 891 To Pr. 899) - Mitsubishi Electric FR-F700PJ Instruction Manual

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

4.15.2 Energy saving monitor (Pr. 891 to Pr. 899)

From the power consumption estimated value during commercial power supply operation, the energy saving
effect by use of the inverter can be monitored/output.
Parameter
Name
Number
DU/PU main display data
52
selection
FM terminal function
54
selection
Cumulative power monitor
891
digit shifted times
892
Load factor
Energy saving monitor
893
reference (motor capacity) 
Control selection during
894
commercial power-supply
operation
Power saving rate
895
reference value
896
Power unit cost
Power saving monitor
897
average time
Power saving cumulative
898
monitor clear
Operation time rate
899
(estimated value)
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197)
The above parameters allow their settings to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter
write selection.
 Performing IPM parameter initialization changes the settings. ( Refer to page 85)
Energy saving operation and energy saving monitor
Initial Value
Setting Range
0
0, 5, 8 to 12, 14, 20, 23 to
(output
25, 50 to 55, 61, 62, 64, 100
frequency)
1
1 to 3, 5, 8 to 12, 14, 21, 24,
(output
50, 52, 53, 61, 62
frequency)
0 to 4
9999
9999
100%
30 to 150%
Rated
inverter
0.4 to 15kW
capacity
0
1
0
2
3
0
9999
1
9999
0 to 500
9999
9999
0
9999
1 to 1000h
9999
0
1
10
9999
9999
0 to 100%
9999
9999
Description
50: Power saving monitor
51: Cumulative power saving monitor
50:Power saving monitor
Set the number of times to shift the
cumulative power monitor digit
(Clamps the monitor value at
maximum.)
No shift
(Clears the monitor value when it
exceeds the maximum value.)
Set the load factor for commercial
power-supply operation. Multiplied by
the power consumption rate (page 179)
during commercial power supply
operation.
The motor capacity (pump capacity).
Set when calculating power saving
rate, average power saving rate,
commercial operation power.
Discharge damper control (fan)
Inlet damper control (fan)
Valve control (pump)
Commercial power-supply drive (fixed
value)
Consider the value during commercial
power-supply operation as 100%
Consider the Pr. 893 setting as 100%.
No function
The power unit cost. Displays the
power cost savings on the energy
saving monitor.
No function
Average for 30 minutes
Average for the set time
No function
Cumulative monitor value clear
Cumulative monitor value hold
Accumulation continued
(communication data upper limit 9999)
Accumulation continued
(communication data upper limit
65535)
Set the annual operation ratio
(consider 365 days  24h as 100%).
(Use for calculation of annual power
saving amount.)
No function
4
175