4.21.2 Regeneration avoidance function (Pr. 665, Pr. 882, Pr. 883, Pr. 885, Pr. 886)

This function detects a regeneration status and increases the frequency to avoid the regenerative status.
 Possible to avoid regeneration by automatically increasing the frequency to continue operation if the fan happens to
rotate faster than the set speed due to the effect of another fan in the same duct.
Parameter
Name
Number
Regeneration
882
avoidance operation
selection
Regeneration
883
avoidance operation
level
Regeneration
avoidance
885
compensation
frequency limit value
Regeneration
886
avoidance voltage
gain
Regeneration
665
avoidance frequency
gain
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197)
 Performing IPM parameter initialization changes the settings. (Refer to page 85)
(1)
What is regeneration avoidance function? (Pr. 882, Pr. 883)
When the regeneration load is large, the DC bus voltage rises and an overvoltage fault (E. OV) may occur.
When this bus voltage rise is detected and the bus voltage level reaches or exceeds Pr. 883, increasing the frequency
avoids the regeneration status.
The regeneration avoidance function is always ON when "1" is set in Pr. 882, and activated only during a constant speed
when "2" is set in Pr. 882.
Regeneration avoidance operation example
for acceleration
Pr. 883
During regeneration
avoidance function operation
Regeneration avoidance
operation example for deceleration
Pr. 883
During regeneration
avoidance function operation
262
Setting
Initial Value
Range
0
1
0
2
200V
400
class
VDC
300 to 800V
400V
780
class
VDC
0 to 30Hz
6Hz
9999
100%
0 to 200%
100%
0 to 200%
Regeneration avoidance operation example
for constant speed
Time
Time
Time
Time
Description
Regeneration avoidance function invalid
Regeneration avoidance function is always valid
Regeneration avoidance function is valid only during a constant
speed operation
Bus voltage level at which regeneration avoidance operates. When
the bus voltage level is set to low, overvoltage error will be less apt
to occur. However, the actual deceleration time increases.
The set value must be higher than the "power supply voltage 
Limit value of frequency which rises at activation of regeneration
avoidance function.
Frequency limit invalid
Responsiveness at activation of regeneration avoidance.
A larger setting will improve responsiveness to the bus voltage
change. However, the output frequency could become unstable.
When vibration is not suppressed by decreasing the Pr. 886 setting,
set a smaller value in Pr. 665.
Pr. 883
During regeneration avoidance
function operation
2
" *.
Time
Time