Function assignment of external terminal and control
4.11 Function assignment of external terminal and control
Purpose
Assign function to input terminal
Set MRS signal (output shutoff) to
NC contact specification
Assign start signal and forward/
reverse command to other signals
Assign function to output terminal
Detect output frequency
Detect output current
Remote output function
Detect specified output power
4.11.1 Input terminal function selection (Pr. 178 to Pr. 182)
Use these parameters to select/change the input terminal functions.
Parameter
Number
STF terminal function
178
selection
STR terminal function
179
selection
AU terminal function
180
selection
RM terminal function
181
selection
RH terminal function
182
selection
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197)
The setting value "60" is only available for Pr.178.
The setting value "61" is only available for Pr.179.
134
Input terminal function
selection
MRS input selection
Start signal (STF/STR)
operation selection
Output terminal function
selection
Up-to-frequency
sensitivity
Output frequency
detection
Speed detection
hysteresis
Output current detection
Zero current detection
Remote output
Pulse train output of
output power
Initial
Name
Value
60
61
4
1
2
Parameter that should be Set
Pr. 178 to Pr. 182
Pr. 190, Pr. 192
Pr. 41 to Pr. 43, Pr. 870
Pr. 150 to Pr. 153, Pr. 166, Pr. 167
Pr. 495, Pr. 496
Initial Signal
STF (forward rotation command)
STR (reverse rotation command)
AU (terminal 4 input selection)
RM (middle speed operation
command)
RH (high-speed operation
command)
Refer to Page
Pr. 17
Pr. 250
Pr. 799
Setting Range
0 to 5, 7, 8, 10, 12, 14, 16, 24, 25,
60, 61, 62, 64 to 67, 72, 9999
134
136
138
140
144
146
148
149