Frequency Setting By Analog Input (Terminal 2, 4); Analog Input Selection (Pr. 73, Pr. 267) - Mitsubishi Electric FR-F700PJ Instruction Manual

Air-conditioning inverter
Hide thumbs Also See for FR-F700PJ:
Table of Contents

Advertisement

4.17 Frequency setting by analog input (terminal 2, 4)

Purpose
Selection of voltage/current input
(terminal 2, 4)
Perform forward/reverse rotation by
analog input.
Noise elimination at the analog input
Adjustment (calibration) of analog
input frequency and voltage (current)

4.17.1 Analog input selection (Pr. 73, Pr. 267)

You can select the function that switches between forward rotation and reverse rotation according to the analog input
terminal specifications and input signal.
Parameter
Name
Number
73
Analog input selection
Terminal 4 input
267
selection
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197)
(1)
Selection of analog input specifications
For the terminal 2 for analog voltage input, 0 to 5V (initial value) or 0 to 10V can be selected.
Either voltage input (0 to 5V, 0 to 10V) or current input (4 to 20mA initial value) can be selected for terminal 4 used for
analog input.
Change the input specifications to change Pr. 267 and voltage/current input switch.
Rated specifications of terminal 4 change according
to the voltage/current input switch setting.
Voltage input: Input resistance 10k
Maximum permissible input voltage
20VDC
Current input: Input resistance 233
Maximum permissible input voltage
30mA

Frequency setting by analog input (terminal 2, 4)

Parameter that should be Set
Analog input selection
Input filter
Bias and gain of frequency
setting voltage (current)
Setting
Initial Value
Range
0
1
1
10
11
0
0
1
2
1k
5
Current input (initial setting)
Voltage input
Pr. 73, Pr. 267
Pr. 74
Pr. 125, Pr. 126, Pr. 241,
C2 to C7 (Pr. 902 to Pr. 905)
Description
Terminal 2 input 0 to 10V
Without reversible operation
Terminal 2 input 0 to 5V
Terminal 2 input 0 to 10V
With reversible operation
Terminal 2 input 0 to 5V
Voltage/current input
switch
Terminal 4 input 4 to 20mA
Terminal 4 input 1 to 5V
Terminal 4 input 2 to 10V
Refer to Page
183
187
188
Description
4
183

Advertisement

Table of Contents
loading