Misoperation prevention and parameter setting restriction

4.18.2 Parameter write disable selection (Pr. 77)

You can select whether write to various parameters can be performed or not. Use this function to prevent parameter
values from being rewritten by misoperation.
Parameter
Number
77
Parameter write selection
The above parameter can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197)
Pr. 77 can always be set independently from the operation mode and operation status.
(1)
Write parameters only during stop (setting "0", initial value)
Parameters can be written only during a stop in the PU operation mode.
The shaded parameters in the parameter list (page 64) can always be written regardless of the operation mode and
operating status. However, Pr. 72 PWM frequency selection and Pr. 240 Soft-PWM operation selection can be written when the
inverter is running in the PU operation mode, but cannot be written in the External operation mode.
(2)
Disable parameter write (setting "1")
Parameter write is not enabled.
(Read is enabled.)
Parameter clear and all parameter clear cannot be
performed, either.
The parameters given on the right can be written even if Pr.
77 = "1".
(3)
Write parameters during operation (setting "2")
Parameters can always be written.
The following parameters cannot be written when the inverter is running even if Pr. 77 = "2". Stop the inverter when
changing their parameter settings.
Parameter
Number
Stall prevention operation level compensation
23
factor at double speed
40
RUN key rotation direction selection
48
Second stall prevention operation current
60
Energy saving control selection
Stall prevention operation reduction starting
66
frequency
71
Applied motor
79
Operation mode selection
80
Motor capacity
82
Motor excitation current
83
Rated motor voltage
Parameters referred to
Pr. 79 Operation mode selection
196
Name
Initial Value
Name
Refer to page 200
Setting Range
0
1
0
2
Parameter
Number
22
75
77
79
160
296
297
997
Parameter
Number
84
Rated motor frequency
90
Motor constant (R1)
96
Auto tuning setting/status
178 to 182
(input terminal function selection)
190, 192
(output terminal function selection)
261
Power failure stop selection
298
Frequency search gain
450
Second applied motor
561
PTC thermistor protection level
800
Control method selection
998
IPM parameter initialization
999
Automatic parameter setting
Description
Write is enabled only during stop.
Parameter can not be written.
Parameter write is enabled in any operation
mode regardless of operation status.
Name
Stall prevention operation level
Reset selection/disconnected PU detection/
PU stop selection
Parameter write selection
Operation mode selection
Extended function display selection
Password lock level
Password lock/unlock
Fault initiation