Causes and corrective actions
Operation panel
E.PE
indication
Name
Parameter storage device fault (control circuit board)
Description
Appears when a fault occurred in the stored parameters. (EEPROM fault)
Check point
Check for too many number of parameter write times.
Please contact your sales representative.
Corrective action
When performing parameter write frequently for communication purposes, set "1" in Pr. 342 to enable RAM write. Note
that powering OFF returns the inverter to the status before RAM write.
Operation panel
E.PUE
indication
Name
PU disconnection
 This function stops the inverter output if communication between the inverter and PU is suspended, e.g. the
parameter unit (FR-PU04/FR-PU07) is disconnected, when "2", "3", "16" or "17" was set in Pr. 75 Reset selection/
disconnected PU detection/PU stop selection.
 This function stops the inverter output when communication errors occurred consecutively for more than permissible
Description
number of retries when a value other than "9999" is set in Pr. 121 Number of PU communication retries during the RS-
485 communication with the PU connector. (Use Pr. 502 Stop mode selection at communication error to change.)
 This function also stops the inverter output if communication is broken within the period of time set in Pr. 122 PU
communication check time interval during the RS-485 communication with the PU connector.
 Check that the parameter unit cable is connected properly.
 Check the Pr. 75 setting.
Check point
 Check that RS-485 communication data is correct. And check that the settings of communication parameter at
inverter match settings of the computer.
 Check that data is transmitted from the computer within a time set in Pr. 122 PU communication check time interval.
 Connect the parameter unit cable securely.
Corrective action
 Check the communication data and communication settings.
 Increase the Pr. 122 PU communication check time interval setting. Or set "9999" (no communication check).
Operation panel
E.RET
indication
Name
Retry count excess
If operation cannot be resumed properly within the number of retries set, this function trips the inverter.
Description
This function is available only when Pr. 67 Number of retries at fault occurrence is set.
When the initial value (Pr. 67 = "0") is set, this protective function is not available.
Check point
Find the cause of fault occurrence.
Corrective action
Eliminate the cause of the error preceding this error indication.
E.5
Operation panel
indication
E.CPU
Name
CPU fault
Description
Stops the inverter output if the communication fault of the built-in CPU occurs.
Check point
Check for devices producing excess electrical noises around the inverter.
 Take measures against noises if there are devices producing excess electrical noises around the inverter.
Corrective action
 Please contact your sales representative.
Operation panel
E.CDO
indication
Name
Output current detection value exceeded
Description
This function is activated when the output current exceeds the Pr. 150 Output current detection level setting.
Check the settings of Pr. 150 Output current detection level, Pr. 151 Output current detection signal delay time, Pr. 166 Output
Check point
current detection signal retention time, Pr. 167 Output current detection operation selection. (Refer to page 146)
Operation panel
E.IOH
indication
Name
Inrush current limit circuit fault
Description
This function is activated when the resistor of the inrush current limit circuit overheats. The inrush current limit circuit fault
Check point
Check that frequent power ON/OFF is not repeated.
Configure a circuit where frequent power ON/OFF is not repeated.
Corrective action
If the problem still persists after taking the above measure, please contact your sales representative.
306
FR-PU04
Corrupt Memry
FR-PU07
FR-PU04
PU Leave Out
FR-PU07
FR-PU04
Retry No Over
FR-PU07
Fault 5
FR-PU04
FR-PU07
CPU Fault
FR-PU04
Fault 14
FR-PU07
OC detect level
FR-PU04
Fault 14
FR-PU07
Inrush overheat