Frequency setting by external terminals

4.7
Frequency setting by external terminals
Purpose
Make frequency setting by
combination of terminals
Perform Jog operation
Infinitely variable speed setting by
terminals
4.7.1

Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)

Can be used to change the preset speed in the parameter with the contact signals.
Any speed can be selected by merely turning ON/OFF the contact signals (RH, RM, RL, REX signals).
Parameter
Number
Multi-speed setting (high
4
speed)
Multi-speed setting (middle
5
speed)
Multi-speed setting (low
6
speed)
24
Multi-speed setting (speed 4)
25
Multi-speed setting (speed 5)
26
Multi-speed setting (speed 6)
27
Multi-speed setting (speed 7)
232 
Multi-speed setting (speed 8)
233
Multi-speed setting (speed 9)
234
Multi-speed setting (speed 10)
235
Multi-speed setting (speed 11)
236
Multi-speed setting (speed 12)
237
Multi-speed setting (speed 13)
238
Multi-speed setting (speed 14)
239
Multi-speed setting (speed 15)
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.

The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 197)

Performing IPM parameter initialization changes the settings. (Refer to page 85)
(1)
Multi-speed setting for 3 speeds (Pr. 4 to Pr. 6)
 The inverter operates at frequencies set in Pr. 4 when RH signal is ON, Pr. 5 when RM signal is ON and Pr. 6 when RL
signal is ON.
 For the RL signal, set "0" in any of Pr.178 to Pr.182 (input terminal function selection) to assign the function to a terminal.
Speed 1
(High speed)
Speed 2
(Middle speed)
ON
RH
ON
RM
RL
REMARKS
In the initial setting, if two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency of
the lower signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
The RH and RM signals are assigned to the terminals RH and RM in the initial setting. By setting "1 (RM)" or "2 (RH)" in any of
Pr. 178 to Pr. 182 (input terminal function selection), you can assign the signals to other terminals.
106
Multi-speed operation
Jog operation
Remote setting function
Name
Initial Value
60Hz
30Hz
10Hz
Speed 3
(Low speed)
Time
ON
Parameter that should be Set
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,
Pr. 232 to Pr. 239
Setting Range

0 to 400Hz
0 to 400Hz
0 to 400Hz
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
9999
0 to 400Hz, 9999
Forward
rotation
Multi-Speed Operation
Connection Example
Pr. 15, Pr. 16
Pr. 59
Description
Frequency when RH turns ON
Frequency when RM turns ON
Frequency when RL turns ON
Frequency from 4 speed to 15 speed can
be set according to the combination of
the RH, RM, RL and REX signals.
9999: not selected
Inverter
STF
RH
10
RM
2
RL
5
SD
Refer to Page
106
108
110