PID monitor function
The PID control set point, measured value and deviation value can be displayed on the operation panel and output from
the terminal FM.
In the deviation monitor, a negative percent can be displayed as an integer, like 0% as 1000 and so on. (The deviation
monitor cannot be output from the terminal FM.)
For each monitor, set the following value in Pr. 52 DU/PU main display data selection and Pr. 54 FM terminal function selection.
Setting
Monitor Description
52
PID set point
53
PID measured value
54
PID deviation
* When neither of C42(Pr. 934) nor C44(Pr. 935) setting is "9999", minimum increment changes from % to no unit, and the full scale value for the terminal FM
changes from 100% to the larger value between C42(Pr. 934) PID display bias coefficient and C44(Pr. 935) PID display gain coefficient. (The smaller value between
C42(Pr. 934) and C44(Pr. 935) becomes the minimum value.)
(9)
Adjustment procedure
Parameter setting
Terminal setting
Turn ON the X14 signal.
Operation
Special operation and frequency control
Minimum
Terminal FM
Increments 
Full Scale 
0.1%
100%/C42(Pr.934) or
0.1%
C44(Pr.935)
0.1%
Adjust the PID control parameters, Pr. 127 to Pr. 134, Pr 553, Pr. 554
and Pr. 575 to Pr. 577.
Set the I/O terminals for PID control (Pr. 178 to Pr. 182 (input terminal
function selection), Pr. 190 or Pr. 192 (output terminal function selection))
When X14 signal is not assigned, setting a value other than "0" in Pr.
128 activates PID operation.
Remarks
Value cannot be set to Pr. 54.
Displays 1000 when the PID deviation is 0%.