Environmental Specifications

The operating and non-operating environmental specifications for the system are
described in
.
TABLE C-3
Environmental Specifications
TABLE C-3
Parameter
Operating
Temperature
Humidity
Altitude
Vibration
Shock
Declared Acoustics
Non-Operating
Temperature
Humidity
Altitude
Vibration
Shock
Handling Drops
Threshold Impact
Value
5˚C to 35˚C (41˚F to 95˚F)—IEC 60068-2-1&2
20% to 80% RH noncondensing; 27˚C (81˚F) wet bulb—
IEC 60068-2-3&56
0 to 3000 meters (0 to 10,000 feet)—IEC 60068-2-13
2
.0001 (z-axis only) G
/Hz, 5-150 Hz, -12db/octave slope,
150-500 Hz— IEC 60068-2-13
3g peak, 11 milliseconds half-sine pulse—IEC 60068-2-27
72 DbA
-20˚C to 60˚C (-4˚F to 140˚F)—IEC 60068-2-1&2
95% RH noncondensing—IEC 60068-2-3&56
0 to 12,000 meters (0 to 40,000 feet)—IEC 60068-2-13
.001 (z-axis only) G
2
/Hz, 5-150 Hz, -12db/octave slope,
150-500 Hz— IEC 60068-2-13
10g peak, 11 milliseconds half-sine pulse—IEC 60068-2-27
25 mm (10 in)
1 meter/second
Appendix C