Advanced Function Setting Level - Omron E5AN-H User Manual

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Advanced Function Setting Level

5-10 Advanced Function Setting Level

242
The advanced function setting level is used for optimizing Controller perfor-
mance. To move to this level, input the password ("−169") from the initial set-
ting level.
To be able to enter the password, the Initial Setting/Communications Protect
parameter in the protect level must be set to 0. (The default is 0.)
• The parameters in this level can be used when the Initial Setting/Commu-
nications Protect parameter is set to 0.
• To switch between setting levels, press the O Key.
• To change set values, press the U and D Keys.
Power ON
Operation
Level
PID Setting
Level
Press the
O Key
Press the O Key
for at
for at least 1 s.
least 3 s.
Initial Setting
Level
Press the O Key
for at least 1 s.
Advanced Function
Setting Level
Adjustment
Level
Press the
O Key less than 1 s.
Bank Setting
Level
C
25.0
Press the O Key for at
least 3 s.
100.0
Control stops.
Communi-
cations
Setting
Level
Press the
O Key for less than 1 s.
Password input
set value −169
Control in progress
Control stopped
Section 5-10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents