Setting the SP Upper and Lower Limit Values
Parameters
4-6-2

Setting

Setting the Set Point Upper-limit Value
Operating Procedure
Input Type
in-t
5
Set Point
C
sl-h
Upper-limit
1300.0
C
sl-h
1000.0
Setting range
Upper limit value changed
Input type changed
Set value
Sensor upper/lower limit values
Symbol
sl-h
Set Point Upper Limit: Initial setting level
sl-l
Set Point Lower Limit: Initial setting level
Set the set point upper and lower limits in the Set Point Upper Limit and Set
Point Lower Limit parameters in the initial setting level. In this example, it is
assumed that the input type is set to a K thermocouple with a temperature
range of −200.0 to 1300.0°C.
−200.0
−100.0
Set Point Upper Limit = 1000
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Set Point Upper Limit parameter.
3. Use the U and D Keys to set the parameter to 1000.0.
Input setting range
Set point limiter
Upper limit
value changed
C
Upper/lower limit values
Parameter: level
Input setting range
Set point limiter
1000.0
Section 4-6
Set point
B
A
(Cannot be set.)
Set point
Set point
B
(Can be set.)
Description
To limit the SP setting
To limit the SP setting
1300.0