Omron E5AN-H User Manual page 204

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Operation Level
lcr1
Leakage Current 1 Monitor
Function
Monitor
See
See
lcr2
Leakage Current 2 Monitor
Function
Monitor
See
See
This parameter measures the heater current from the CT input used for
detecting SSR short-circuits.
The heater current is measured and the leakage current 1 monitor is dis-
played.
• HS alarms are not detected if the control output (heating) OFF time is
100 ms or less.
Monitor range
0.0 to 55.0
• ffff is displayed when 55.0 A is exceeded.
• If an HS alarm 1 alarm is output, the HA indicator will light and the No. 1
display for the leakage current 1 monitor will flash.
■ Related Parameters
HS alarm 1, HS alarm 2 (adjustment level): Page 197
Failure detection (advanced function setting level): Page 257
Error displays lcr1: Page 306
This parameter measures the heater current from the CT input used for
detecting SSR short-circuits.
This parameter measures and displays the heater current value.
• HS alarms are not detected if the control output (heating) OFF time is
100 ms or less.
Monitor range
0.0 to 55.0
• ffff is displayed when 55.0 A is exceeded.
• If an HS alarm 2 alarm is output, the HA indicator will light and the No. 1
display for the leakage current 2 monitor will flash.
■ Related Parameters
HS alarm 1, HS alarm 2 (adjustment level): Page 197
HS alarm use (advanced function setting level): Page 257
Error displays lcr2: Page 306
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
The HS Alarm Use parameter must
be set to ON.
Unit
A
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported (two CTs).
Alarm 1 must be assigned.
The HS Alarm Use parameter must
be set to ON.
Unit
A
Section 5-3
183

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents