Calibrating the Transfer Output
2. Press the M Key to switch to the Transfer Output Screen.
str
no
3. The 20 mA Calibration Screen will be displayed. Use the U and D Keys to adjust
a20.t
52ac
4. The 4 mA Calibration Screen will be displayed. Use the U and D Keys to adjust
a4.t
0037
5. Press the U Key. The No. 2 display changes to yes. Release the key and wait two
str.t
no
6. The calibration mode is quit by turning the power OFF.
the DMM monitor value to 20 mA, and then press the M Key. The contents of the
calibration will be temporarily registered.
the DMM monitor value to 4 mA, and then press the M Key. The contents of the
calibration will be temporarily registered.
seconds or press the M Key. This stores the temporarily registered calibration data
to EEPROM.
To cancel the saving of temporarily registered calibration data to EEPROM, press
the M Key (while no is displayed in the No. 2 display) without pressing the U Key.
Section 6-6
293