Using the Simple Program Function

4-16 Using the Simple Program Function

4-16-1 Simple Program Function

Parameters Related to the Simple Program Function
Parameter name
Symbol
ptrn
Program Pattern
prst
Program Start
Bank ∗ Soak Time
∗ sok
(See note 2.)
t-u
Soak Time Unit
Bank ∗ Wait Band
∗ wtb
(See note 2.)
sktr
Soak Time Remain
Monitor
pbnk
Valid Program Bank
(See note 3.)
Note
132
• A simple program consists of multiple banks.
The program can be created from the required number of banks by speci-
fying the end bank in the Valid Program Bank parameter.
A simple program can be started from any of the banks from bank 0 to the
end bank. When operation is finished in one bank, the program switches
to the next bank and operation starts in that bank. Operation after the end
bank has been completed can be set in the Program Pattern parameter.
• The program starts when the Program Start parameter is changed from
RSET to STRT.
• The program stops when the Program Start parameter is changed from
STRT to RSET. The program can be reset in any bank.
Wait band 0
SP0
SP1
Soak time 0
(Bank 0)
Set (monitor) values
OFF, STOP, CONT, LOOP
RSET, STRT
0 to 9999
m (minutes)/h (hours)
Temperature: OFF, 0.1 to 3,240.0
Analog: OFF, 0.01 to 99.99
0 to 9999
0 to 7
(1) The setting unit is %FS for analog inputs.
(2) When the Soak Time or Wait Band parameter is changed in the adjust-
ment level, the changes will be reflected in the current bank.
(3) Displayed when the Program Pattern parameter is set to any value other
than OFF. The bank cannot be switched to any other bank.
Wait band n
Wait band 1
Soak time 1
(Bank 1)
Unit
---
---
min or h
---
°C or °F (See note 1.)
min or h
---
Section 4-16
SPn
Soak time n
(Bank n)
Display level
Initial setting level
Operation level
Bank setting level
Advanced function set-
ting level
Bank setting level
Operation level
Initial setting level