Omron E5AN-H User Manual page 267

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Advanced Function Setting Level
hbu
HB ON/OFF
Function
Setting
hbl
Heater Burnout Latch
Function
Setting
See
See
246
• Set to use the heater burnout alarm.
Setting range
on: Enabled, off: Disabled
• When this parameter is set to ON, the heater burnout alarm is held until
either of the following conditions is satisfied.
a
Heater burnout detection is set to 0.0 A.
b
The power is cycled.
c
The latch is cancelled by the PF Key.
(PF Setting = LAT: Alarm Latch Cancel)
d
The latch is cancelled by an event input.
(Event Input Assignment 1 to 4 = LAT: Alarm Latch Cancel)
• Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
Setting range
on: Enabled, off: Disabled
■ Related Parameters
Event input assignment 1 to 4 (initial setting level): Page 238
HB ON/OFF: Page 246, PF setting: Page 273 (advanced function setting
level)
Section 5-10
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
Default
on
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
The Heater Burnout Detection
parameter must be set to ON.
Default
off

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents