Omron E5AN-H User Manual page 148

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Using the Transfer Output
Operating Procedure
Operation Level
PV/SP
C
25.0
100.0
Initial Setting Level
Input Type
in-t
5
Initial Setting Level
Transfer Output
tr-t
Type
off
tr-t
sp
Initial Setting Level
Transfer Output
C
tr-h
Upper Limit
1300.0
C
tr-h
200.0
Initial Setting Level
Transfer Output
C
tr-l
Lower Limit
-200.0
Output current (mA)
20
4
0
10
Transfer output
lower limit
(The above graph is for when the linear current output is set to 4 to 20 mA.)
The following procedure sets the transfer output for an SP range of −50 to
200.
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Transfer Output Type parameter by pressing the M Key.
3. Press the U Key to select sp (set point).
4. Select the Transfer Output Upper Limit parameter by pressing the M Key.
5. Use the D Key to set the parameter to 200.0. The default is 1300.0.
6. Select the Transfer Output Lower Limit parameter by pressing the M Key.
MV (%)
100
90
Transfer output
upper limit
Section 4-14
127