Setting The No. 3 Display; Pv/Sp Display Selection - Omron E5AN-H User Manual

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Setting the No. 3 Display

3-11 Setting the No. 3 Display

3-11-1 PV/SP Display Selection

Note
MV Display for
Heating and Cooling
Control
82
This section describes how to set the No. 3 Display (E5AN/EN-H). The bank
No., MV, or soak time remain can be displayed on the No. 3 display.
The following table shows the set values and display contents for the PV/SP
Display selection.
Set value
0
Only PV/SP is displayed (with no No. 3 display.)
1
PV/SP/Bank No. and PV/SP/MV are displayed in order. (See note 2.)
2
PV/SP/MV and PV/SP/Bank No. are displayed in order. (See note 2.)
3
Only PV/SP/Bank No. is displayed.
4
Only PV/SP/MV is displayed. (See note 2.)
5
PV/SP/Bank No. and PV/SP/Soak time remain are displayed in order.
6
PV/SP/MV and PV/SP/Soak time remain are displayed in order. (See
note 2.)
7
Only PV/SP/Soak time remain is displayed.
(1) The default setting is 4.
(2) For details on setting the MV for heating and cooling control, refer to MV
Display for Heating and Cooling Control below. The MV for position-pro-
portional models becomes the value for opening the valve.
When 1, 2, 5, or 6 is selected, press the M Key to display the next value set
for the PV/SP display (display 2).
Example: When the PV/SP Display Screen Parameter Is Set to 2
Operation Level
PV/SP (Display 1)
Press the
25.0
C
M
key
100.0
50.0
PV/SP/MV
Select either the manipulated variable (heating) or manipulated variable (cool-
ing) as the MV to be displayed for PV/SP/MV during heating and cooling con-
trol. This parameter is displayed only when heating/cooling control is being
performed and PV/SP/MV is selected in the PV/SP Display Screen parameter
or a Monitor/Setting Item Display parameter. This setting can be made for
standard models only.
Parameter name
MV Display Selection
O
C-O
Display contents
PV/SP (Display 2)
C
25.0
100.0
b.0
PV/SP/Bank No.
Set value
Symbol
o
c-o
Section 3-11
Display contents
Manipulated variable
(heating)
Manipulated variable
(cooling)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h