Alarm Outputs
Bank 1
C
1.a-1
Alarm Value 1
0.0
C
1.a-1
10.0
PV Change Rate Alarm
SP Alarms When Remote
SP Is Used
70
6. Press the M Key to select the Bank 1 Alarm Value 1 parameter.
7. Use the U Key to set 10.0.
The change width can be found for PV input values in any set period. Differ-
ences with previous values in each set period are calculated, and an alarm is
output if the result exceeds the alarm value. The PV rate of change calculation
period can be set in units of 60 ms.
If a positive value is set for the alarm value, the PV will operate as a change
rate alarm in the rising direction. If a negative value is set, the PV will operate
as a change rate alarm in the falling direction.
Precaution
If a shorter PV rate of change calculation period is set, outputs set for the PV
change rate alarm function may repeatedly turn ON and OFF for a short
period of time. It is therefore recommended that the PV change rate alarm be
used with the alarm latch turned ON.
PV
Alarm value
0
ON
OFF
Alarm function
Parameter name
Setting range
PV Rate of Change
1 to 999
Calculation Period
RSP Absolute Upper Limit and RSP Absolute Lower Limit parameters were
added for the E5AN-H and E5EN-H (with remote SP input). These parame-
ters are used for a remote SP regardless of whether the SP mode is set to
Remote SP or Local SP Mode.
PV change width for PV rate
of change calculation period
ON
OFF
Unit
Sampling cycle
17
(= 17 × 60 ms = 1,020 ms)
Section 3-9
Time
Default