Operation Level; Adjustment Level; Initial Setting Level; Advanced Function Setting Level - Omron E5C series User Manual

Digital temperature controllers
Hide thumbs Also See for E5C series:
Table of Contents

Advertisement

Basic Setting Levels

Operation Level

This level is displayed automatically when the power supply is turned ON.
This level is used for the SP, alarm values, and other basic settings and monitoring.
Normally, select this level for operation.

Adjustment Level

This level is used to set the PID constants and to perform tuning, such as autotuning.
In Adjustment Level, the settings of the parameters can be changed during operation. This is not
possible in the Initial Setting Level or Advanced Function Setting Level.

Initial Setting Level

This level is used for the most basic settings.
It is used to set the input type and other parameters.
Use it to set the input type, alarm type, and other basic settings.

Advanced Function Setting Level

This level is used for advanced settings.
Use it to assign functions to the control outputs and auxiliary outputs.
You will not be able to enter the Advanced Function Setting Level with the default settings.
To enter the Advanced Function Setting Level, first disable Initial Setting/Communications Protection
and then enter the password (−169) at the amov (Move to Advanced Function Setting Level)
parameter in the Initial Setting Level.
Use the following procedure to move to Advanced Function Setting Level.
Step 1:
Press the
O
+
M
simultaneously for at least 3 s.
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
E5@C Digital Temperature Controllers User's Manual (H174)
Power ON
Level changes automatically.
Operation Level
Used for SP, alarm
values, and other basic
settings and monitoring.
Step 3:
Keys
Press the
Protect Level
Used to set protection
for operations.
Step 2: Change the parameter with the
M
Key and change the setting of the icpt parameter to 0.
icpt
Initial Setting/Communications Protect
0
Set 0. Default: 1
Move to Protect Level.
Display icpt (Initial Setting/Communications Protect) and set it to 0.
Return to Operation Level.
Return to Initial Setting Level.
Display amoV (Move to Advanced Function Setting Level) and then enter −169.
3 Part Names and Basic Procedures
Step 4:
O
Key for at least 3 s
Initial Setting Level
Used to set the input
type and other basic
settings.
Step 5: Enter −169 for the amov parameter.
a
amov
O
+
M
Keys for at least 1 s.
Advanced Function
Setting Level
Advanced settings
Move to Advanced Function Setting Level parameter
0
Enter −169. Default: 0
3 - 11
3