Advanced Function Setting Level
lbab
LBA Band
Function
Setting
See
See
260
• This parameter sets the LBA band.
• If a control deviation greater than the LBA band is not reduced when the
LBA level is exceeded, an loop burnout is detected.
Note For ON/OFF control, the LBA Detection Time parameter (advanced
function setting level) must not be set to 0. For 2-PID control, the
LBA Detection Time parameter must not be set to 0 for any of PID
sets 1 to 8.
Models
Temperature input
Analog input
■ Related Parameters
Process value/Set point (operation level): Page 177
Alarm 1 type (initial setting level): Page 231
LBA detection time, LBA level (advanced function setting level): Page 259
Alarm 1 must be assigned.
The alarm type must be set to 12
(LBA).
The LBA detection time must not be
0. (See note.)
Setting range
Unit
°C or °F
0.0 to 3240.0
0.00 to 99.99
%FS
Section 5-10
Default
3.0
0.20