Omron E5AN-H User Manual page 224

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Adjustment Level
soak
Soak Time
Function
Setting
See
See
wt-b
Wait Band
Function
Setting
See
See
• This parameter sets the time for the control operation when using the sim-
ple program function.
• The set value is saved in the Soak Time parameter for the current bank.
Setting range
1 to 9999
min or h
■ Related Parameters
Program start, Soak time remain (operation level): Page 184
Bank * wait band, Bank * soak time (Bank setting level): Page 215
Program pattern (initial setting level): Page 229
Soak time unit (advanced function setting level): Page 266
• This parameter sets the stable band within which the soak time is mea-
sured for the simple program function.
• The set value is saved in the Soak Time parameter for the current bank.
Model
Temperature input
Analog Input
■ Related Parameters
Program start, Soak time remain (operation level): Page 184
Bank * wait band, Bank * soak time (Bank setting level): Page 215
Program pattern (initial setting level): Page 229
Soak time unit (advanced function setting level): Page 266
The Program Pattern parameter
must not be set to OFF.
Unit
Default
1
The Program Pattern parameter
must not be set to OFF.
Setting range
OFF or 0.1 to
3240.0
OFF or 0.01 to
99.99
Section 5-4
Unit
Default
°C or °F
off
%FS