Using Event Inputs
4-5-2

Operation Commands Other than Bank Selection

Note
Executing Run/Stop
Control
Switching between
Auto and Manual
Control
98
The following table shows the functions assigned when an Event Input
Assignment (1 to 4) is displayed.
Setting
none
None
stop
RUN/STOP
manu
Auto/Manual
prst
Program Start (See note 1.)
drs
Invert Direct/Reverse Operation
rsp
SP Mode Switch (See note 2.)
at-2
100% AT Execute/Cancel
at-1
40% AT Execute/Cancel (See note 3.)
wtpt
Setting Change Enable/Disable
cmwt
Communications Write Enable/Disable (See note 4.)
lat
Alarm Latch Cancel
(1) PRST (Program Start) can be set even when the Program Pattern param-
eter is set to OFF, but the function will be disabled.
(2) This function can be selected only with models that support remote SP.
(3) This function can be set for heating/cooling control, but the function will
be disabled.
(4) This function can be selected only with models that support communica-
tions. Also, when a work bit is selected as event input data, Communica-
tions Write Enable/Disable parameter cannot be selected.
When any of the following functions is set for an Event Input Assignment
parameter, the same function cannot be set for another Event Input Assign-
ment parameter: STOP (RUN/STOP), MANU (Auto/Manual Switch), PRST
(Program Start), DRS (Direct/Reverse Operation), RSP (SP Mode Switch),
AT-2 (100% AT Execute/Cancel), AT-1 (40% AT Execute/Cancel), WTPT (Set-
ting Change Enable/Disable), CMWT (Communications Write Enable/Dis-
able), or LAT (Alarm Latch Cancel).
Turn event inputs ON and OFF while the power is being supplied. Event input
ON/OFF changes are detected for inputs of 50 ms or longer. (However, inputs
of 250 ms or longer is determined using logic operation.)
The functions are described in detail below. Event inputs 1 and 2 are taken as
examples. When using event inputs 3 and 4, substitute event input 3 for event
input 1 and event input 4 for event input 2.
When the Event Input Assignment 1 or Event Input Assignment 2 parameter
is set to STOP (RUN/STOP), control is started when event input 1 or 2 turns
OFF. Control is stopped when the input turns ON. Alarm outputs, however, will
be according to the process value.
The STOP indicator will light while control is stopped.
Setting
Event input 1 or 2
Event input 1 or 2
When the Event Input Assignment 1 or Event Input Assignment 2 parameter
is set to MANU (auto/manual), manual control will start when event input 1 or
2 turns ON. Auto control will start when the input turns OFF.
Function
Input contact
ON
OFF
Section 4-5
Status
STOP
RUN