Adjustment Level
mv-s
MV at Stop
Function
Setting
See
See
mv-e
MV at PV Error
Function
Setting
See
See
204
• This parameter sets the MV to use when the RUN/STOP status changes
from RUN to STOP.
Setting range
Standard control: −5.0 to 105.0
Heating/cooling control: −105.0 to 105.0
Position-proportional control (close, with the
Direct Setting of Position Proportional MV
parameter ON): −5.0 to 105.0
Position-proportional control (floating or
with the Direct Setting of Positional Propor-
tional MV parameter OFF): CLOS, HOLD,
OPEN
■ Related Parameters
RUN/STOP (operation level): Page 185
MV at stop and error addition (advanced function setting level): Page 256
• This parameter sets the MV to use when an input error occurs.
Setting range
Standard control: −5.0 to 105.0
Heating/cooling control: −105.0 to 105.0
Position-proportional control (close, with the
Direct Setting of Position Proportional MV
parameter ON): −5.0 to 105.0
Position-proportional control (floating or
with the Direct Setting of Positional Propor-
tional MV parameter OFF): CLOS, HOLD,
OPEN
■ Related Parameters
MV at stop and error addition (advanced function setting level): Page 256
Section 5-4
The control must be set to 2-PID
control.
The MV at Stop and Error Addition
parameter must be ON.
Unit
Default
%
0.0
None
HOLD
The control must be set to 2-PID
control.
The MV at Stop and Error Addition
parameter must be ON.
Unit
Default
%
0.0
None
HOLD