Omron E5AN-H User Manual page 219

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Adjustment Level
See
See
lcr2
Leakage Current 2 Monitor
Function
Monitor
See
See
hs2
HS Alarm 2
Function
Setting
198
■ Related Parameters
Leakage current 1 monitor (adjustment level): Page 197
HS alarm, HS alarm latch, HS alarm hysteresis (advanced function setting
level): Page 257
This parameter measures the heater current from the CT input used for
detecting SSR short-circuits.
This parameter measures and displays the heater current value.
• HS alarms are not detected if the control output (heating) OFF time is
100 ms or less.
Monitor range
0.0 to 55.0
• ffff is displayed when 55.0 A is exceeded.
• If an HS alarm 2 alarm is output, the HA indicator will light and the No. 1
display for the leakage current 2 monitor will flash.
■ Related Parameters
HS alarm 1, HS alarm 2 (adjustment level): Page 197
HS alarm use (advanced function setting level): Page 257
Error displays lcr2: Page 306
This parameter sets the current for the HS alarm to be output.
• An HS alarm is output when the leakage current value exceeds the set-
ting of this parameter.
• When the set value is 50.0, the HS alarm output is turned OFF. When the
set value is 0.0, the HS alarm output will turn ON.
Setting range
0.0 to 50.0
A
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported (two CTs).
Alarm 1 must be assigned.
The HS Alarm parameter must be
set to ON.
Unit
A
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported (two CTs).
Alarm 1 must be assigned.
The HS Alarm parameter must be
set to ON.
Unit
Default
50.0
Section 5-4