Adjustment Level
of-r
Manual Reset Value
Function
Setting
See
See
hys
Hysteresis (Heating)
chys
Hysteresis (Cooling)
Function
Parameter
name
Hysteresis
Setting
(Heating)
Hysteresis
(Cooling)
See
See
202
• This parameter sets the required manipulated variable to remove offset
during stabilization of P or PD control.
Setting range
0.0 to 100.0
%
■ Related Parameters
PID * integral time (PID setting level): Page 217
PID ON/OFF (initial setting level): Page 228
This parameter sets the hysteresis for ensuring stable operation at the ON/
OFF switching point.
• For standard control, use the Hysteresis (Heating) parameter. The Hyster-
esis (Cooling) parameter cannot be used.
• For heating/cooling control, the hysteresis can be set independently for
heating/cooling. The Hysteresis (Heating) parameter is used for the heat-
ing side, and the Hysteresis (Cooling) parameter is used for the cooling
side.
Model
Temperature input
Analog Input
Temperature input
Analog Input
■ Related Parameters
PID ON/OFF, Standard or heating/cooling (initial setting level): Page 228
The control must be standard control
and 2-PID control.
The Integral Time parameter for PID
sets 1 to 8 must be set to 0.
Unit
Default
50.0
The control must be ON/OFF control.
For the Hysteresis (Cooling) parame-
ter, the control must be heating/cool-
ing control.
Setting range
0.1 to 3240.00
0.01 to 99.99
0.1 to 3240.00
0.01 o 99.99
Section 5-4
Unit
Default
°C or °F
1.0
%FS
0.10
°C or °F
1.0
%FS
0.10