Operation Level
bank
Bank No.
Function
Operation
See
See
rsp
Remote SP Monitor
Function
Monitor
See
See
• This parameter is used to select the bank. The SP, PID set number, SP
ramp set value, alarm value, soak time, and wait band are set in bank set-
ting level for each bank to be used, and then operation is switched
between the banks using bank specifications (with event inputs, key oper-
ations, or communications).
• With this parameter, the bank is specified by using key operations.
• Use the U and D Keys to specify the bank number.
• The default is for the current bank number to be displayed.
■ Related Parameters
Bank numbers used (advanced function setting level): Page 237
• This parameter monitors the remote SP while in Local SP Mode.
• While in Remote SP Mode, the remote SP can be monitored on the No.
2 display of the PV/SP Screen.
Monitor range
Remote SP lower limit to remote
SP upper limit
There are restrictions on the SP
limits.
■ Related Parameters
Process value/Set point (operation level): Page 177
SP mode (adjustment level): Page 193
Remote SP upper limit, Remote SP lower limit (advanced function setting
level): Page 267
Remote SP enable (advanced function setting level): Page 266
The Bank Numbers Used parameter
must be set to 0.
The ST parameter must be set to
OFF.
The Remote SP Enable parameter
must be set to ON.
The SP Mode parameter must be set
to LSP.
Unit
EU
Section 5-3
179