Initial Setting Examples

3-1

Initial Setting Examples

Explanation of Examples
Example 1
Input type:
Control method: ON/OFF control
Alarm type:
Alarm value 1:
Set point:
46
Initial hardware setup, including the sensor input type, alarm types, control
periods, and other settings is done using parameter displays. The O and M
Keys are used to switch between parameters, and the amount of time that you
press the keys determines which parameter you move to.
This section describes 3 typical examples.
Changing Parameters
in-t
0
in-h
100
M
M
in-l
0
M
cntl
cntl
pid
pid
Setup Procedure
5 (K thermocouple,
−200.0°C to 1,300.0°C)
Power ON
2 (upper limit)
20°C (deviation)
100°C
Initial Setting
Level
Set input
specifications
Set control
specifications
Set alarm type
Operation
Level
Set alarm values
Start operation
A
image means that there are parameters.
Continue pressing the M key to change parameters
until you reach the intended parameter.
Changing Numbers
C
25.0
Numeric data and selections in each
0.0
screen can be changed by using the
U and D keys.
Power ON
Operation
Level
C
25.0
0.0
Press the O key for
at least 3 s.
Initial Setting
Level
in-t
Check input type.
M
Check that
cntl
control method is
onof
ON/OFF control.
M
alt1
Check alarm type.
M
Press the O key for
at least 1 s.
Operation
Level
C
25.0
Use the U and
D keys to set the
100.0
SP to 100°C.
M
r-s
Confirm that
control is running.
run
M
Use the U and
C
al-1
D keys to set the
20.0
alarm value to
20°C.
M
Start operation.
Section 3-1
PV/SP
Control stops.
Input Type: 5
5
ON/OFF
onof
control:
PID
pid
control:
Alarm 1 Type: 2
2
Control starts.
PV/SP:
100.0
Running
run
Stopped:
stop
Alarm Value 1:
20.0