E5AN-H/EN-H Output Unit Ratings
Model
Output type
E53-RN
Relay
E53-QN
Voltage (PNP)
E53-Q3
Voltage (NPN)
E53-Q4
Voltage (PNP)
E53-C3N
4 to 20 mA
E53-C3DN
0 to 20 mA
E53-V34N
0 to 5 V
E53-V35N
0 to 10 V
HB, HS, and Heater Overcurrent Alarms (for E5CN/AN/EN-H Controllers with Heater
Burnout, HS, and Heater Overcurrent Alarms)
Max. heater current
Input current readout accuracy
Heater burnout alarm setting
range
HS alarm setting range
Heater overcurrent alarm setting
range
Note
(1) When the control output 1 ON time is less than 100 ms, heater burnout detection, heater overcurrent
detection, and heater current measurement are not performed.
(2) When the control output 1 OFF time is less than 100 ms, HS alarm, and leakage current measure-
ment are not performed.
Characteristics
Indication accuracy
(ambient temperature of
23°C)
Temperature variation
influence (See note 2.)
Voltage variation influence
(See note 2.)
Hysteresis
298
Output form
ON/OFF
250 VAC, 5 A (resistive load), electrical durability: 100,000 opera-
tions
ON/OFF
PNP type, 12 VDC, 40 mA (with short-circuit protection)
ON/OFF
NPN type, 24 VDC, 20 mA (with short-circuit protection)
ON/OFF
PNP type, 24 VDC, 40 mA (with short-circuit protection)
4 to 20 mA DC, Load: 600 Ω max., Resolution: approx. 10,000
Linear
0 to 20 mA DC, Load: 600 Ω max., Resolution: approx. 10,000
Linear
Linear
0 to 10 VDC, Load: 1 kΩ max., Resolution: approx. 10,000
Linear
0 to 5 VDC, Load: 1 kΩ max., Resolution: approx. 10,000
50 A AC
±5% FS ±1 digit max.
0.1 to 49.9 A (0.1 A units)
0.0 A:
50.0 A:
Min. detection ON time: 100 ms (See note 1.)
0.1 to 49.9 A (0.1 A units)
0.0 A:
50.0 A:
Min. detection OFF time: 100 ms (See note 2.)
0.1 to 49.9 A (0.1 A units)
0.0 A:
50.0 A:
Min. detection OFF time: 100 ms
Thermocouple (See note 1.):
(±0.1% of indication value or ±1°C, whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.1% of indication value or ±0.5°C, whichever is greater) ±1 digit max.
Analog input: ±0.1% FS ±1 digit max.
CT input: ±5% FS ±1 digit max.
Thermocouple (R, S, B, W, PLII)
(±1% of PV or ±10°C, whichever is greater) ±1 digit max.
Other thermocouples:
(±1% of PV or ±4°C, whichever is greater) ±1 digit max.
*K thermocouple at −100°C max: ±10°C max.
Platinum resistance thermometer:
(±1% of PV or ±2°C, whichever is greater) ±1 digit max.
Analog input: ±1% FS ±1 digit max.
Temperature Input
Analog Input
Specifications
Heater burnout alarm output turns OFF.
Heater burnout alarm output turns ON.
HS alarm output turns ON.
HS alarm output turns OFF.
Heater overcurrent alarm output turns ON.
Heater overcurrent alarm output turns OFF.
0.1 to 3240.0°C or °F
(in units of 0.1°C or °F)
0.01% to 99.99% FS (in units of 0.01% FS)
Appendix