Omron E5AN-H User Manual page 248

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Initial Setting Level
sl-h
SP Upper Limit
sl-l
SP Lower Limit
Function
Setting
See
See
• These parameters set the upper and lower limits of the set points. A set
point can be set within the range defined by the upper and lower limit set
values in the SP Upper Limit and SP Lower Limit parameters. If these
parameters are reset, any set point that is outside of the new range will be
forcibly changed to either the upper limit or the lower limit.
• When the temperature input type and temperature unit have been
changed, the set point upper limit and set point lower limit are forcibly
changed to the upper and lower limits of the sensor.
• During temperature input, the decimal point position depends on the cur-
rently selected sensor, and during analog input it depends on the Decimal
Point parameter setting.
Controllers with Thermocouple/Resistance Thermometer Universal Inputs
Parameter
name
Set Point
Temperature
Upper Limit
Analog
Set Point
Temperature
Lower Limit
Analog
■ Related Parameters
Input type: Page 224, Temperature unit: Page 226 (initial setting level)
Setting range
SP lower limit + 1 to Input set-
ting range upper limit
SP lower limit + 1 to scaling
upper limit
Input setting range lower limit
to SP upper limit − 1
Scaling lower limit to SP
upper limit − 1
Section 5-9
Unit
Default
EU
1300.0
EU
−200.0
EU
EU
227

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents